Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-0425-00752
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/15/2025 | Commercial Electrical | APPROVED | |||
| 05/28/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/28/2025 | Commercial Mechanical | REQUIRES RESUBMIT | Provide returns for rooms 140, 143, and 145 to avoid using the corridor as a return duct. [Initial comment: Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2018.] | ||
| 05/14/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |