Permit Number: TC-COM-0425-00752
Parcel: 13405118S

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.3

Permit Number - TC-COM-0425-00752
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2025 Commercial Electrical APPROVED
06/03/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/03/2025 Commercial Mechanical REQUIRES RESUBMIT Comment not addressed. Provide returns for rooms 140, 143, and 145 to avoid using the corridor as a return duct. [Second comment: Provide returns for rooms 140, 143, and 145 to avoid using the corridor as a return duct.] [Initial comment: Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2018.]
06/03/2025 PDSD Application Completeness Express REVIEW COMPLETED