Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.3
Permit Number - TC-COM-0425-00752
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/03/2025 | Commercial Electrical | APPROVED | |||
| 06/03/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/03/2025 | Commercial Mechanical | REQUIRES RESUBMIT | Comment not addressed. Provide returns for rooms 140, 143, and 145 to avoid using the corridor as a return duct. [Second comment: Provide returns for rooms 140, 143, and 145 to avoid using the corridor as a return duct.] [Initial comment: Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2018.] | ||
| 06/03/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |