Permit Number: TC-COM-0425-00725
Parcel: 13355230A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0425-00725
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2025 Site Zoning APPROVED
05/01/2025 Water - PDSD APPROVED
05/05/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/05/2025 Commercial Building REQUIRES RESUBMIT April 24, 2025
1st Review

Intertech Architectural Interiors
Attn: Maria Oldham
6089 E. Grant Road
Tucson, Arizona 85712

Re: V’S BARBERSHOP
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0425-00662
Stantec Project Number: 185215066
Stantec File Number: TUC-25-048

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B II-A 1,039 21 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907]] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

STRUCTURAL COMMENTS

There are no comments.
MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

General

1. Please provide a calculation for the water pressure drop from the service to the last remote fixture having the most demanding pressure. [Ref. IPC 2018 Sec. 604]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
05/05/2025 Commercial Electrical REQUIRES RESUBMIT April 24, 2025
1st Review

Intertech Architectural Interiors
Attn: Maria Oldham
6089 E. Grant Road
Tucson, Arizona 85712

Re: V’S BARBERSHOP
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0425-00662
Stantec Project Number: 185215066
Stantec File Number: TUC-25-048

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B II-A 1,039 21 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907]] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

STRUCTURAL COMMENTS

There are no comments.
MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

General

1. Please provide a calculation for the water pressure drop from the service to the last remote fixture having the most demanding pressure. [Ref. IPC 2018 Sec. 604]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
05/05/2025 Commercial Mechanical REQUIRES RESUBMIT April 24, 2025
1st Review

Intertech Architectural Interiors
Attn: Maria Oldham
6089 E. Grant Road
Tucson, Arizona 85712

Re: V’S BARBERSHOP
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0425-00662
Stantec Project Number: 185215066
Stantec File Number: TUC-25-048

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B II-A 1,039 21 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907]] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

STRUCTURAL COMMENTS

There are no comments.
MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

General

1. Please provide a calculation for the water pressure drop from the service to the last remote fixture having the most demanding pressure. [Ref. IPC 2018 Sec. 604]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
05/05/2025 Commercial Plumbing REQUIRES RESUBMIT April 24, 2025
1st Review

Intertech Architectural Interiors
Attn: Maria Oldham
6089 E. Grant Road
Tucson, Arizona 85712

Re: V’S BARBERSHOP
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0425-00662
Stantec Project Number: 185215066
Stantec File Number: TUC-25-048

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B II-A 1,039 21 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907]] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

STRUCTURAL COMMENTS

There are no comments.
MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

General

1. Please provide a calculation for the water pressure drop from the service to the last remote fixture having the most demanding pressure. [Ref. IPC 2018 Sec. 604]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
04/21/2025 Fire New Construction REVIEW COMPLETED Fire Sprinklers alterations requires a separate permit.
04/17/2025 PDSD Application Completeness Express REVIEW COMPLETED