Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0425-00710
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/06/2025 | Commercial Building Standard | APPROVED | |||
| 04/24/2025 | Commercial Electrical Standard | APPROVED | |||
| 05/08/2025 | Site Engineering Standard | APPROVED | |||
| 05/06/2025 | Water - PDSD Standard | APPROVED | |||
| 05/08/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/06/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Sections C403.1.1 and C502.2.3, IECC 2018. 2. Clarify the items to be stored. The ventilation system appears to be designed for S-1 Storage. Reference: Section 107.2.1, IBC 2018. |
||
| 05/06/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Clarify how the “water filler” located at the existing sink serves as a point of use water dispenser. The use of a point-of-use water dispenser in lieu of a drinking fountain requires the installation of a listed and labeled dispenser along with a permanently mounted disposable cup dispenser. The cup dispenser shall be located adjacent to the water dispenser with the dispensing end between 34” and 48” above the finished floor. See: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/2008-21_e_drinkingfountainpolicy.pdf | ||
| 04/24/2025 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Outdoor Lighting Review TC-COM-0425-00710 (423 N TUCSON BL TUCSON, AZ 85716) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Outdoor Lighting Review: 1. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your table and use the same number on your site plan 2. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1. 3. Show compliance with total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. E1.1 – Lighting Code section 104.2.2. 4. Show compliance with shielding requirements and light trespass per 401.3. 5. Submit catalogue or specification sheets of all proposed new outdoor lighting fixtures illustrating the type of fixture, color temperature, lumens rating and whether full cut-off or unshielded. 6. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. 7. Specify any exceptions used. 8. Provide Curfew lighting controls If applicable Per section 403. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 05/07/2025 | Site Zoning Standard | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-0425-00710 423 N TUCSON BL. - C-1 Use Unknown (1st Review) TRANSMITTAL DATE: May 7, 2025 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the C-1 zone (UDC 4.7.20). Use Unknown 1. Clarify what the use is as designated in the UDC. Commercial Services is a use group not a use. 2. As it appears that you are removing vehicle parking spaces to provide access to the proposed overhead door a development package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf. The DP is a separate submittal from the building plans. The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 04/24/2025 | Fire New Construction Standard | REVIEW COMPLETED | Any fire sprinklers upgrades requires a separate permit per the 2018 IFC. | ||
| 04/16/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |