Permit Number: TC-COM-0425-00696
Parcel: 11450030A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0425-00696
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2025 Site Zoning APPROVED
04/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/28/2025 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Sheet A3.0: Please amend the plans to show compliance with IBC Section 1012 Ramps
A. Please add a note or otherwise indicate the maximum cross-slope is 1 in 48 or 2%. Across the direction of travel. IBC 1012.3
B. Please provide dimensioned plans showing a minimum of 36” clear between the ramp handrails. IBC 1012.5.1
C. Please show handrails on both sides of the ramp as the rise is over 7” IBC 1012.8
2. Please amend the plans to show the Stairway and Ramp handrail extensions extend horizontally above the landing 12 inches minimum beyond the bottom of stairways and ramp runs. The extensions of handrails shall be in the same direction of the flights of stairs at stairways and the ramp runs at ramps. IBC 1014.6
3. Please amend the plans to note or otherwise indicate door handles, pulls, latches, locks, and other operable parts on accessible doors shall have a shape that is easy to grasp with one hand and does not require tight grasping, pinching, or twisting of the wrist to operate. 2009 ICC A117.1 404.2.6
4. Please amend the plans to note or otherwise indicate door surfaces within 10 inches of the floor, measured vertically, shall be a smooth surface on the push side extending the full width of the door. 2009 ICC A117.1 404.2.9
5. Please amend the plans to list any required special inspections and provide a statement of special inspections with required special inspections and tests. For example, Soils (fill under slab and fill supporting interior wall foundation. IBC 107.2.1 & 1704.1
A. Additionally, provide the City of Tucson Special Inspection Certificate(s) with Parts A and B completed with the next submittal. IBC 107.1 SI form link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
04/28/2025 Site Engineering REQUIRES RESUBMIT TC-COM-0425-00696
8920 E WOODLAND RD

Site engineering comments are as follows:
1. This project lies within a recognized floodplain, Tanque Verde Creek, and requires a Floodplain Use Permit (FUP) with an elevation certificate.
2. The CMU retaining wall beneath the structure will also require flood venting. These shall be in accordance with the requirements of NFIP Technical Bulletin 1. The vents must be no higher than one foot above the adjacent grade. They shall be located on two sides of the structure and measure 1 square inch per 1 square foot of floor gross floor area.
https://www.fema.gov/sites/default/files/2020-07/fema_tb1_openings_foundation_walls_walls_of_enclosures_031320.pdf

Please start a new FUP at our permit application web page:
https://tdc-online.tucsonaz.gov/#/home

Note: Construction of new buildings require elevation one foot above the base flood elevation. For all new construction buildings, two elevation certificates must be filled out by a registered land surveyor and submitted to the City, one before the foundation is poured and one after construction is completed.
Ryan Insalaco – ryan.insalaco@tucsonaz.gov
04/21/2025 Fire New Construction REVIEW COMPLETED
04/14/2025 PDSD Application Completeness Express REVIEW COMPLETED