Permit Number: TC-COM-0425-00684
Parcel: 124150090

Address:
831 E 17TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0425-00684
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2025 Site Zoning Standard APPROVED
05/01/2025 Water - PDSD Standard APPROVED
04/22/2025 Outdoor Lighting Standard NOT REQUIRED
05/05/2025 Site Engineering Standard NOT REQUIRED
05/05/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/02/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Sheet CS-1: Please update CODES to remove references to the 2018 International Residential (IRC)Codes and the applicable code from our list of Governing codes. IBC 107.2.1 For example, see bellow list.
2018 International Building Code (IBC)
2018 International Existing Building Code (IEBC)
2009 ICC A117.1 Accessibility Code (by reference)
2018 International Mechanical Code (IMC)
2018 International Plumbing Code (IPC)
2017 National Electrical Code (NEC)
2018 International Fire Code (IFC)
2018 International Fuel Gas (IFGC)
2018 International Energy Conservation Code (IECC)
City of Tucson/Pima County Outdoor Lighting Code
Local Amendments to Above Codes ( www.tucsonaz.gov/pdsd/building-codes )
2. Sheet CS-1: Please provide a detailed description of the work involved in this permit’s scope. IBC 105.3 What is being remodeled into what? Are walls being demoe’d? Are new walls being erected? The addition of a three-compartment sink, grease interceptor, hood, etc.
3. Sheet A-1: Please amend the plans to show doors serving a space with ≥ 50 persons swing in the direction of egress travel. IBC 1010.1.2.1
3. Sheet A-1: Please amend the plans to note or otherwise indicate doors serving a space with ≥ 50 persons in A occupancies have panic hardware. IBC 1010.1.10
4. Sheet A-1: Please amend the egress plans to show exit signs are shown at doors, as required to direct egress, and every 100 feet. IBC 1013.1 Additionally, please amend the plans to show the method and locations of emergency illumination provided by IBC 1008.3 For example, bug eye with battery backup.
5. Please amend the plans to show the new counters and self-service shelves meet accessibility requirements of IBC 1109.12.3 and 1109.12.4. For example, a portion of the counter an shelving is required to be accessible. Please refer to 2009 ICC A117.1 Chapter 9 for technical requirements.
6. Please amend the plans to provide structural construction drawings and details showing the method of connecting the new hood to the existing roof framing members. IBC 107.2.7
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
04/23/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0425-00684 (831 E 17TH ST TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Provide GFCI protection for ALL kitchen receptacles per NEC 210.8(B)(2).
2. Provide GFCI protection for receptacle within 6 feet of sinks, per NEC 210.8(B)(5). See circuit L4-19.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
05/02/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Clarify the balancing data for EF-4. The Exhaust Fan Schedule calls for 100 CFM of exhaust but the Air Balance Schedule calls for 150 CFM o0f exhaust.
2. The Air Balance Schedule shows 450 CFM of outside air being transferred. What is the source of this transferred air?
05/02/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Verify that the grease interceptor will be installed within the property lines. Reference: Section 107.2.6, IBC2018.
2. All water outlets or direct-connection of water to an appliance shall be protected against backflow. Specify the device to be used for each outlet or appliance connection. Reference: Sections 608.3 and 608.16, IPC 2018
3. Provide a cleanout at the junction of the building drain and the building sewer (i.e., within 30” of the exterior wall of the building). Reference: Section 708.1.3, IPC 2018.
04/23/2025 Fire New Construction Standard REVIEW COMPLETED The following items apply to the proposed project:
1. Fire alarm or fire sprinklers alterations requires a separate permit.
2. Page M-2, Kitchen hood schedule-Type 2 hood requires a separate permit for hood fire suppression.
3. If Applicable: Co2 Systems requires a separate permit.
Per the 2028 International Fire Code.
04/12/2025 PDSD Application Completeness Express REVIEW COMPLETED