Permit Number: TC-COM-0425-00684
Parcel: 124150090

Address:
831 E 17TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0425-00684
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2025 Commercial Building Standard APPROVED
05/27/2025 Commercial Electrical Standard APPROVED
06/16/2025 Commercial Mechanical Standard APPROVED
06/11/2025 Water - PDSD Standard APPROVED
06/16/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/16/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Comment not addressed. [Initial comment: Provide a cleanout at the junction of the building drain and the building sewer (i.e., within 30” of the exterior wall of the building). Reference: Section 708.1.3, IPC 2018.]
2. The specified grease interceptor is listed for use with 4” inlet/outlets, not 3” inlets/outlets. Reference: Sections 303.2 and 706.2, IPC 2018.
05/23/2025 PDSD Application Completeness Express REVIEW COMPLETED