Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL REVISION v.1
Permit Number - TC-COM-0425-00664
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/03/2025 | Commercial Electrical Standard | APPROVED | |||
| 11/04/2025 | Site Engineering Standard | APPROVED | |||
| 11/12/2025 | Site Zoning Standard | APPROVED | |||
| 11/17/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/17/2025 | Commercial Building Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0425-00664 ADDRESS/PARCEL: (104 E PRINCE RD TUCSON, AZ 85705) COMMENTS: 1. Site Plan a. The location of the doors do not match the floor plan. b. Please correct this. 2. Roof Gutter a. The contractor proposed a gutter and drain system. It is not reflected within these drawings. Ensure that it empties in a location that the flow will be accommodated as described by the contractor. Please correct this on the drawings. b. NOTE: If the above is not executed, City of Tucson Site Engineering will require you to install a trench drain between the asphalt and the new concrete sidewalk all the way to the front of the property. 3. Weep Screed a. It is not clear how the weep screed is addressed. b. Please place the proper callout on the plan, informing us as to which detail drawing is being used at the bottom of the wall(s). c. Weep screed Detail 5/A2.0 and 6/A2.0 is not called out anywhere. Please correct this. 4. Provide a section drawing outside the two exterior doors. Ensure to address the handicap accessible slope on the landings. 5. Please resubmit. Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976. |
||
| 11/10/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018. 2. Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and automatic start-up control (i.e. the thermostat is capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy) and, if the thermostat does not require manual changeover from the heating and cooling modes, it restricts set point overlap. Reference: Section C403.4.2 through C403.4.2.3, IECC 2018. |
||
| 11/12/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 10/21/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |