Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-0425-00661
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/01/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/01/2025 | Commercial Building | REQUIRES RESUBMIT | May 1, 2025 2nd Review Intertech Architectural Interiors Attn: Erin Hastreiter 6089 E. Grant Road Tucson, Arizona 85712 Re: BAYADA HOME HEALTH CARE TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0425-00661 Stantec Project Number: 185215066 Stantec File Number: TUC-25-046 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms B I-A 5,278 79 Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: None. ARCHITECTURAL COMMENTS Sheet G2 1. Previous Comment: The plans appear to exceed common path of egress travel in “Suite 850”. The Egress plan indicates a common path of travel distance of 99’. When scaled at 1/8” = 1’ and measuring the 99’ path of travel indicated the distance measures 103’. The maximum common path of travel distance is 100’. Please revise. [Ref. IBC 2018 Sec. 1006.2.1] Still Required: The revised plan removed the cubicle in the corner and started the travel path at another cubicle. Common path of travel is measured from the most remote point in a room. The location indicated in the revised plan is not the most remote point. Removing the cubicle desk does not allow the travel distance to be reduced to the nearest cubicle. Please revise. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 05/01/2025 | Commercial Electrical | REQUIRES RESUBMIT | May 1, 2025 2nd Review Intertech Architectural Interiors Attn: Erin Hastreiter 6089 E. Grant Road Tucson, Arizona 85712 Re: BAYADA HOME HEALTH CARE TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0425-00661 Stantec Project Number: 185215066 Stantec File Number: TUC-25-046 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms B I-A 5,278 79 Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: None. ARCHITECTURAL COMMENTS Sheet G2 1. Previous Comment: The plans appear to exceed common path of egress travel in “Suite 850”. The Egress plan indicates a common path of travel distance of 99’. When scaled at 1/8” = 1’ and measuring the 99’ path of travel indicated the distance measures 103’. The maximum common path of travel distance is 100’. Please revise. [Ref. IBC 2018 Sec. 1006.2.1] Still Required: The revised plan removed the cubicle in the corner and started the travel path at another cubicle. Common path of travel is measured from the most remote point in a room. The location indicated in the revised plan is not the most remote point. Removing the cubicle desk does not allow the travel distance to be reduced to the nearest cubicle. Please revise. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 05/01/2025 | Commercial Mechanical | REQUIRES RESUBMIT | May 1, 2025 2nd Review Intertech Architectural Interiors Attn: Erin Hastreiter 6089 E. Grant Road Tucson, Arizona 85712 Re: BAYADA HOME HEALTH CARE TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0425-00661 Stantec Project Number: 185215066 Stantec File Number: TUC-25-046 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms B I-A 5,278 79 Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: None. ARCHITECTURAL COMMENTS Sheet G2 1. Previous Comment: The plans appear to exceed common path of egress travel in “Suite 850”. The Egress plan indicates a common path of travel distance of 99’. When scaled at 1/8” = 1’ and measuring the 99’ path of travel indicated the distance measures 103’. The maximum common path of travel distance is 100’. Please revise. [Ref. IBC 2018 Sec. 1006.2.1] Still Required: The revised plan removed the cubicle in the corner and started the travel path at another cubicle. Common path of travel is measured from the most remote point in a room. The location indicated in the revised plan is not the most remote point. Removing the cubicle desk does not allow the travel distance to be reduced to the nearest cubicle. Please revise. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 05/01/2025 | Commercial Plumbing | REQUIRES RESUBMIT | May 1, 2025 2nd Review Intertech Architectural Interiors Attn: Erin Hastreiter 6089 E. Grant Road Tucson, Arizona 85712 Re: BAYADA HOME HEALTH CARE TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0425-00661 Stantec Project Number: 185215066 Stantec File Number: TUC-25-046 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms B I-A 5,278 79 Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: None. ARCHITECTURAL COMMENTS Sheet G2 1. Previous Comment: The plans appear to exceed common path of egress travel in “Suite 850”. The Egress plan indicates a common path of travel distance of 99’. When scaled at 1/8” = 1’ and measuring the 99’ path of travel indicated the distance measures 103’. The maximum common path of travel distance is 100’. Please revise. [Ref. IBC 2018 Sec. 1006.2.1] Still Required: The revised plan removed the cubicle in the corner and started the travel path at another cubicle. Common path of travel is measured from the most remote point in a room. The location indicated in the revised plan is not the most remote point. Removing the cubicle desk does not allow the travel distance to be reduced to the nearest cubicle. Please revise. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 04/30/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |