Permit Number: TC-COM-0425-00654
Parcel: 13710513A

Address:
5600 S 12TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0425-00654
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2025 Site Zoning Standard APPROVED
06/24/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/16/2025 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0425-00654
ADDRESS/PARCEL: (5600 S 12TH AV TUCSON, AZ 85706)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval.

COMMENTS:
1. KIOSK SERVICE ROOM ACCESS DOOR.
a. Doorway clearances ICC A117.1 section 404, clear opening width of 32 inches measured between the face of door & stop with door open 90 degrees.
2. Kiosk Machine: Please comply to the following.
a. Unobstructed forward reach is 48 inches maximum & 15 inches minimum above the floor.
b. Side/parallel approach to an unobstructed element 10 inches away, reach shall be 48 inches maximum and 15 inches minimum above floor.
c. Provide a drawing that illustrates items a and b above are met.
3. Please resubmit.
If you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976
06/05/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0425-00654 (5600 S 12TH AV TUCSON, AZ 85706)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Remove the “Progress” notation from the Architect’s Seal. Preliminary plans cannot be approved.
2. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
3. Provide new and updated panel schedules, showing the circuits that are being modified, added or removed. NEC arts;300 and 408.4.
4. Designate the circuit number, that corresponds to the panel schedule, at the location of each new or modified light fixture, receptacle, and equipment disconnect switch or other outlet, NEC arts;300 and 408.4.
5. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
06/23/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Provide construction documents that are complete and clearly indicate the extent of the proposed work (i.e. remove the “PROGRESS” label from the drawings.). Reference: Section 107.2.1, IBC 2018.
2. Provide calculations to verify that adequate ventilation will be provided. Reference: Section 403.3.1.1, IMC 2018.
06/04/2025 Fire New Construction Standard REVIEW COMPLETED
06/02/2025 PDSD Application Completeness Express REVIEW COMPLETED