Permit Number: TC-COM-0425-00651
Parcel: 11451200B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0425-00651
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/02/2025 Commercial Building Standard REQUIRES RESUBMIT May 1, 2025
1st Review

A23 Studios
Attn: Burak Bekat
711 E. 9th Street
Tucson, Arizona 85719

Re: MISTER CARWASH BEAR CANYON
NEW BUILDING

City of Tucson Permit Number: TC-COM-0425-00651
Stantec Project Number: 185215066
Stantec File Number: TUC-25-043


Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 5,402 22 No No
Separate Permits: Private site sewer and water utilities, exterior signage.
Deferred Submittals: Pre-engineered canopies, pre-engineered trusses, pre-engineered awnings and trellises, and pre-cast trash pit.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, masonry, EFIS, and outdoor lighting.

ARCHITECTURAL COMMENTS

General

1. Provide City of Tucson special inspection certificate(s) with Parts A and B completed, listing earthwork, concrete, epoxy and expansion anchors, masonry, EFIS, and outdoor lighting. Make sure that the owner or their legal representative signs the form.

Sheet T1.0

1. Please clarify on the plans which site utilities are to be permitted separately. The plans provided for permit do not include onsite private water and sewer designs. However Sheet E1.0 does provide onsite electrical design; is this information to be included under this permit?

Sheet A1.0

1. Provide on the site plan the distance from the building(s) to the lot lines and/or adjacent buildings on the same lot, so that fire separation distance, rating of exterior walls, protection of openings and projections can be determined per 2018 IBC Table 602 and Sec. 705. Also, since these dimensions that you going to provide are a condition of the approval of the permit, this site plan cannot be a “reference only” site plan.

STRUCTURAL COMMENTS

Sheet S1.1

1. The special inspection notes indicate special inspection for field welding; however, except the 4’-0” tall site fence there doesn’t appear to be any field welding and a 4’-0” site fence is exempt from a building permit per 2018 IBC Sec. 105.2. Please clarify.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
05/02/2025 Commercial Electrical Standard REQUIRES RESUBMIT May 1, 2025
1st Review

A23 Studios
Attn: Burak Bekat
711 E. 9th Street
Tucson, Arizona 85719

Re: MISTER CARWASH BEAR CANYON
NEW BUILDING

City of Tucson Permit Number: TC-COM-0425-00651
Stantec Project Number: 185215066
Stantec File Number: TUC-25-043


Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 5,402 22 No No
Separate Permits: Private site sewer and water utilities, exterior signage.
Deferred Submittals: Pre-engineered canopies, pre-engineered trusses, pre-engineered awnings and trellises, and pre-cast trash pit.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, masonry, EFIS, and outdoor lighting.

ARCHITECTURAL COMMENTS

General

1. Provide City of Tucson special inspection certificate(s) with Parts A and B completed, listing earthwork, concrete, epoxy and expansion anchors, masonry, EFIS, and outdoor lighting. Make sure that the owner or their legal representative signs the form.

Sheet T1.0

1. Please clarify on the plans which site utilities are to be permitted separately. The plans provided for permit do not include onsite private water and sewer designs. However Sheet E1.0 does provide onsite electrical design; is this information to be included under this permit?

Sheet A1.0

1. Provide on the site plan the distance from the building(s) to the lot lines and/or adjacent buildings on the same lot, so that fire separation distance, rating of exterior walls, protection of openings and projections can be determined per 2018 IBC Table 602 and Sec. 705. Also, since these dimensions that you going to provide are a condition of the approval of the permit, this site plan cannot be a “reference only” site plan.

STRUCTURAL COMMENTS

Sheet S1.1

1. The special inspection notes indicate special inspection for field welding; however, except the 4’-0” tall site fence there doesn’t appear to be any field welding and a 4’-0” site fence is exempt from a building permit per 2018 IBC Sec. 105.2. Please clarify.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
05/02/2025 Commercial Mechanical Standard REQUIRES RESUBMIT May 1, 2025
1st Review

A23 Studios
Attn: Burak Bekat
711 E. 9th Street
Tucson, Arizona 85719

Re: MISTER CARWASH BEAR CANYON
NEW BUILDING

City of Tucson Permit Number: TC-COM-0425-00651
Stantec Project Number: 185215066
Stantec File Number: TUC-25-043


Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 5,402 22 No No
Separate Permits: Private site sewer and water utilities, exterior signage.
Deferred Submittals: Pre-engineered canopies, pre-engineered trusses, pre-engineered awnings and trellises, and pre-cast trash pit.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, masonry, EFIS, and outdoor lighting.

ARCHITECTURAL COMMENTS

General

1. Provide City of Tucson special inspection certificate(s) with Parts A and B completed, listing earthwork, concrete, epoxy and expansion anchors, masonry, EFIS, and outdoor lighting. Make sure that the owner or their legal representative signs the form.

Sheet T1.0

1. Please clarify on the plans which site utilities are to be permitted separately. The plans provided for permit do not include onsite private water and sewer designs. However Sheet E1.0 does provide onsite electrical design; is this information to be included under this permit?

Sheet A1.0

1. Provide on the site plan the distance from the building(s) to the lot lines and/or adjacent buildings on the same lot, so that fire separation distance, rating of exterior walls, protection of openings and projections can be determined per 2018 IBC Table 602 and Sec. 705. Also, since these dimensions that you going to provide are a condition of the approval of the permit, this site plan cannot be a “reference only” site plan.

STRUCTURAL COMMENTS

Sheet S1.1

1. The special inspection notes indicate special inspection for field welding; however, except the 4’-0” tall site fence there doesn’t appear to be any field welding and a 4’-0” site fence is exempt from a building permit per 2018 IBC Sec. 105.2. Please clarify.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
05/02/2025 Commercial Plumbing Standard REQUIRES RESUBMIT May 1, 2025
1st Review

A23 Studios
Attn: Burak Bekat
711 E. 9th Street
Tucson, Arizona 85719

Re: MISTER CARWASH BEAR CANYON
NEW BUILDING

City of Tucson Permit Number: TC-COM-0425-00651
Stantec Project Number: 185215066
Stantec File Number: TUC-25-043


Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 5,402 22 No No
Separate Permits: Private site sewer and water utilities, exterior signage.
Deferred Submittals: Pre-engineered canopies, pre-engineered trusses, pre-engineered awnings and trellises, and pre-cast trash pit.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, masonry, EFIS, and outdoor lighting.

ARCHITECTURAL COMMENTS

General

1. Provide City of Tucson special inspection certificate(s) with Parts A and B completed, listing earthwork, concrete, epoxy and expansion anchors, masonry, EFIS, and outdoor lighting. Make sure that the owner or their legal representative signs the form.

Sheet T1.0

1. Please clarify on the plans which site utilities are to be permitted separately. The plans provided for permit do not include onsite private water and sewer designs. However Sheet E1.0 does provide onsite electrical design; is this information to be included under this permit?

Sheet A1.0

1. Provide on the site plan the distance from the building(s) to the lot lines and/or adjacent buildings on the same lot, so that fire separation distance, rating of exterior walls, protection of openings and projections can be determined per 2018 IBC Table 602 and Sec. 705. Also, since these dimensions that you going to provide are a condition of the approval of the permit, this site plan cannot be a “reference only” site plan.

STRUCTURAL COMMENTS

Sheet S1.1

1. The special inspection notes indicate special inspection for field welding; however, except the 4’-0” tall site fence there doesn’t appear to be any field welding and a 4’-0” site fence is exempt from a building permit per 2018 IBC Sec. 105.2. Please clarify.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
05/02/2025 Outdoor Lighting Standard REQUIRES RESUBMIT May 1, 2025
1st Review

A23 Studios
Attn: Burak Bekat
711 E. 9th Street
Tucson, Arizona 85719

Re: MISTER CARWASH BEAR CANYON
NEW BUILDING

City of Tucson Permit Number: TC-COM-0425-00651
Stantec Project Number: 185215066
Stantec File Number: TUC-25-043


Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 5,402 22 No No
Separate Permits: Private site sewer and water utilities, exterior signage.
Deferred Submittals: Pre-engineered canopies, pre-engineered trusses, pre-engineered awnings and trellises, and pre-cast trash pit.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, masonry, EFIS, and outdoor lighting.

ARCHITECTURAL COMMENTS

General

1. Provide City of Tucson special inspection certificate(s) with Parts A and B completed, listing earthwork, concrete, epoxy and expansion anchors, masonry, EFIS, and outdoor lighting. Make sure that the owner or their legal representative signs the form.

Sheet T1.0

1. Please clarify on the plans which site utilities are to be permitted separately. The plans provided for permit do not include onsite private water and sewer designs. However Sheet E1.0 does provide onsite electrical design; is this information to be included under this permit?

Sheet A1.0

1. Provide on the site plan the distance from the building(s) to the lot lines and/or adjacent buildings on the same lot, so that fire separation distance, rating of exterior walls, protection of openings and projections can be determined per 2018 IBC Table 602 and Sec. 705. Also, since these dimensions that you going to provide are a condition of the approval of the permit, this site plan cannot be a “reference only” site plan.

STRUCTURAL COMMENTS

Sheet S1.1

1. The special inspection notes indicate special inspection for field welding; however, except the 4’-0” tall site fence there doesn’t appear to be any field welding and a 4’-0” site fence is exempt from a building permit per 2018 IBC Sec. 105.2. Please clarify.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
04/28/2025 Site Engineering Standard REQUIRES RESUBMIT TC-COM-0425-00651
8825 E TANQUE VERDE RD

Site engineering comments are as follows:
1. The associated development package, TD-DEV-0425-00097, must be approved by all reviewers and issued prior to the approval of this permit submission. UDC Article 3.3.3.7.a
Ryan Insalaco – ryan.insalaco@tucsonaz.gov
04/28/2025 Site Zoning Standard REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0425-00651 - TD-DEV-0425-00097
8825 E TANQUE VERDE RD. – C-2
Self Service Car Wash (1st Review)

TRANSMITTAL DATE: April 28, 2025

DUE DATE: April 29, 2025

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). Automotive: Self Service Car Wash - is an approved use in the zone (UDC Table 4.8-4), subject to Use Specific Standard 4.9.13.E.

1. COMMENT: As Development Package (DP) TD-DEV-0125-00008 has not completed its first review Zoning will not review the building plans at this time. Once the DP has completed its first review Zoning will review for compliance. Until the DP is approved by all review agencies Zoning cannot approve this building permit.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
04/29/2025 Water - PDSD Standard REQUIRES RESUBMIT 1. An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, etc.). Revise the plumbing site plan to show the installation of the water service to the building and the installation of the building sewer (See C401 in the development package). Reference: Sections 107.2.1 and 107.2.6, IBC 2018.
2. Reduced pressure backflow prevention assemblies are to be located adjacent to the water meter and are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf.
3. Provide the water demand that will be served by the water meter. Reference: Section 107.2.1, IBC 2018.
04/23/2025 Fire New Construction Standard REVIEW COMPLETED Fire extinguishers shall comply with section 906 of the 2024 IFC.