Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2024 Site Engineering APPROVED
07/02/2024 Site Zoning NOT REQUIRED
07/16/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/11/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.
1 The previous electrical plan review comments concerning the Outdoor Lighting Compliance was not addressed completely. Provide evidence on the lighting plan that verifies full compliance with the 2012 City of Tucson Outdoor Lighting Code. See chapter 104.
07/16/2024 Commercial Mechanical REQUIRES RESUBMIT The keynote identifying the roof coating (#5, sheet 19 of 35) has not been revised to comply with the provisions of Table C402.3, IECC 2018. [Initial comment: To qualify as an equipment building, the minimum values of roof solar reflectance and thermal emittance must comply with the provisions of Table C402.3, IECC 2018. Reference: Section C402.1.2, IECC 2018.]
06/27/2024 PDSD Application Completeness Express REVIEW COMPLETED