Permit Number: TC-COM-0424-00751
Parcel: 117092000

Address:
1110 S 6TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0424-00751
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/10/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1, 504, 606.1, and 607.3, IPC 2018.
2. Show how the new water piping relates to the existing water supply system and show that the additional connections do not cause the existing piping to be overloaded. Reference: Section 107.2.1, IBC 2018.
3. Specify the material of construction for the above and below ground sanitary drainage and vent pipes. Reference: Sections 702.1 and 702.2, IPC 2018.
4. Show the location of all cleanouts for the new building drain. Reference: Section 708.1.1, IPC 2018.
06/11/2024 Commercial Structural REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0524-00906
ADDRESS/PARCEL: (7655 S KOLB RD TUCSON, AZ 85756)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:
1. Previously, I reviewed and approved a building permit #TC-COM-0423-00973. That permit showed the space as an Assembly Area (Art Gallery & Entrance).
2. This permit application is turning the above space into an Alcoholic Beverage Service (Bar) area.
3. Please submit a complete set of construction documents including Architectural, Mechanical, Electrical, Plumbing, etc. Please ensure that all drawings sheets are sealed/signed/dated by a Licensed Architect in Arizona (this required for all commercial projects).
4. Please resubmit.
06/11/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-COM-0424-00751
1110 S 6th Ave. Tucson, AZ. – C-3
Interior alterations and new water heater location(1st Review)

TRANSMITTAL: June 11, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-2 zone (UDC 4.7.9). A multifamily is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.

2. Until a DP is submitted and approved Zoning cannot approve the DP.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
06/10/2024 Water - PDSD REQUIRES RESUBMIT Show the location and size of the water meter, backflow preventer, and the water service pipe on a site plan. Reference: Section 107.2.1 and 107.2.6, IBC 2018.
05/09/2024 PDSD Application Completeness Express REVIEW COMPLETED