Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0424-00744
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/13/2024 | Commercial Electrical | APPROVED | |||
| 05/15/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/14/2024 | Commercial Building | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0424-00744 ADDRESS/PARCEL: (4984 E 22ND ST TUCSON, AZ 85711) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. COMMENTS: 1. Detail 1/A2.1: Missing cant strip. Please provide a detail drawing between the new roof and existing wall. 2. This note below is on sheet A1.3 upper right keynotes. However, no plumbing drawings are submitted. “MEDGAS PLUMBER TO INSTALL COPPER OXYGEN-TRANSFER PIPES BETWEEN NEW OXYGEN ROOM AND EXISTING OXYGEN ROOM. VERIFY LOCATION IN FIELD. REFER TO AIRNETIC SITE PREP GUIDE FOR SPECIFICATIONS.” 3. Provide information to the ramp in front of the door complying to the accessibility requirements such as slope of ramp, etc. 4. The walls have a 1 hour fire rating. Should the door have a fire rating complementing the 1 hour walls? Just asking the question. 5. Please confirm that the existing walls are also 1 hour fire rated. 6. Please resubmit. |
||
| 05/15/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Provide a mechanical design for the installation of the Airnetic oxygen generators. Reference: Section 107.2.1, IBC 2018. | ||
| 05/15/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Show the size, route, and specifications (e.g. valves?) for the Oxygen connection pipes. Reference: Section 107.2.1, IBC 2018. 2. Clarify the termination point for the overflow roof drain noted on sheet A2.1. Reference: Sections 1108.2, IPC 2018. |
||
| 05/10/2024 | Site Engineering | REQUIRES RESUBMIT | 1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plans and is submitted in the TDC Online Portal. Mike Ortiz michael.ortiz@tucsonaz.gov |
||
| 05/14/2024 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review PROJECT: TC-COM-0424-00744 4984 E 22nd St – C-2 Building Addition (1st Review) TRANSMITTAL: May 14, 2024 Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the C-2 zone (UDC 4.7.21). Animal Services is an allowed use in the zone (UDC Table 4.8-4) subject to Use Specific Standards 4.9.4.D.1, .2, .3, & .4 and 4.9.13.P or 4.9.4.D.7 & 4.9.4.D.10-.15. 1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. As Development Package DP17-0218 is still open a revision to this DP is required showing the proposed addition. This revision must be approved prior to approval the building permit. If you have any questions about this transmittal, contact Nicholas Martell at Nicholas.Martell@tucsonaz.gov. |
||
| 05/09/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 04/29/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |