Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0424-00739
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2024 | Site Zoning | APPROVED | |||
| 05/10/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/10/2024 | Commercial Building | REQUIRES RESUBMIT | Please submit your revised documents along with a detailed response letter, which states how all Building Review Section comments were addressed. This submittal is not complete and further comments could arise after the next submittal. 1. Please amend Code Analysis Data to Include the 2018 IEBC International Building Code IBC 107.2.1 2. Please amend the plan to provide dimensions for all doors and indicate the type of hardware is being used. 3. Please amend plans to indicate the type of I-4 facility this will be. IBC 308.1 For example, is there personal care, custodial care or medical care is provided for people who, due to age, physical limitations, diseases, mental disabilities or other infirmities, need a supervised environment (see the commentary for the definitions of “Personal care,” “Custodial care” and “Medical care”). This includes persons who are ambulatory and are capable of self-preservation as well as those who are restricted in their mobility or are totally immobile to the extent that they are incapable of self-preservation and therefore may need assistance to evacuate during an emergency situation, such as a fire. Additionally, please indicate the hours of service. 4. Provide illumination for the means of egress, including the exit discharge per IBC 1008. Show compliance with the following: A. The means of egress shall be illuminated at all times the building space is occupied. B. The means of egress illumination level shall not be less than 1 foot-candle at the walking surface. C. The means of egress illumination shall be supplied by backup power (consisting of storage batteries, unit equipment, or an on-site generator) for a duration of not less than 90 minutes. IBC 1008.3 5. Amend plans so Exit signs are shown at doors, as required to direct egress, and every 100 feet. IBC 1013.1 6. IEBC 305.7 requires that accessibility be provided to the altered spaces. Where the existing path of travel elements, which entails a primary entrance, a primary path of travel, sanitary facilities serving the area, and signs. Otherwise, accessibility upgrades shall be required in accordance with IEBC.305.7. 1. If the cost of providing or upgrading the items above to be accessible is disproportionate to the cost of construction (exceeds 20% of the cost of construction not including accessibility upgrades), please provide information to verify construction costs. If this exemption is taken, accessibility upgrades equaling 20% of the cost of the project shall be made. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 05/07/2024 | Fire New Construction | REQUIRES RESUBMIT | Fire Sprinkler/Fire Alarm are required for an I-4 Occupancy in accordance with IFC 2018, 903.2.6 & 907.2.6. Questions: patricia.shelton@tucsonaz.gov |
||
| 04/25/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |