Permit Number: TC-COM-0424-00723
Parcel: 13214024E

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0424-00723
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2024 Site Engineering NOT REQUIRED
05/28/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/23/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Please show in the electrical site and floor plans how the 3 electrical plans submitted, ‘E3 - Panel schedules’ for panels ‘MDP-1A’, ‘MDP-1B', ‘MDP-2A', ‘MDP-2B’, ‘BLDG A-UNIT PANEL (TYP)’, ‘BLDG B-UNIT PANEL (TYP)’, and ‘E4 - FAULT CALCULATIONS’ and ‘E5 - ELEC DETAILS (Penetrations)’ correlate with the scope of work described as “Cosmetic update to building exterior and room interiors, and vandalized items”. Describe in detail the scope of electrical work proposed for each area associated with this project and reflect this on the electrical power and lighting site and floor plans.

Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
05/28/2024 Commercial Mechanical REQUIRES RESUBMIT Provide a mechanical design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. Reference: Sections 107.1 and 107.2.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
05/28/2024 Commercial Plumbing REQUIRES RESUBMIT Provide a plumbing design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. Reference: Sections 107.1 and 107.2.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
05/24/2024 Commercial Structural REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0424-00723
ADDRESS/PARCEL: (810 E BENSON HY Unit:BLDG 1 TUCSON, AZ 85713)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:
1. Submit separate permit for each of the following: 1. Building #1, 2. Building #2, 3. Swimming Pool.
2. Submit a complete Code Analysis to include, 1. A closer look at the fire sprinkler requirement for a multi story Hotel structure. 2. A closer look at IBC 1107.6.1.1 Accessible units. The type A and type B unit requirements and Accessible units must be dispersed among the different types of units. Show your calculation clearly. Please locate/label them on the floor plan.
3. All commercial permit require a seal/signature/date by an Arizona Registered Architect, Mechanical, Electrical, Plumbing on all drawings.
4. Substantial alteration is present. Submit complete layout of existing bathroom fixture layout in the Architectural Floor Plan. Submit complete Mechanical, Electrical and Plumbing drawings.
5. You are proposing updating the exterior of the building. On the exterior elevations, identify and notate exactly what is being done. All exterior elevations are void of information.
6. Show your parking calculation as well as how many handicap stalls are required and reflect them on the site plan. Locate the bicycle racks as well please.
7. Please resubmit.
04/29/2024 Fire New Construction REQUIRES RESUBMIT -Indicate if the buildings meet the fire alarm requirement of IFC 1103.7.5.1.
john.vincent@tucsonaz.gov
5203495581
05/23/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0424-00723
810 E BENSON HY .- C-2
Site Fence (1st Review)

TRANSMITTAL: May 23, 2024
This site is located in the C-2 zone (UDC 4.7.21).

1. This plan calls out the use as “HOTEL” but the last approved development package, DP22-0243 calls the use as Travelers Accommodation, Lodging. Clarify what the use is.

2. The parking layout shown on A001 does not match what is shown on the last approved development package, DP22-0243. Either provide an approved DP that shows the layout reflected on A001 or submit a new DP for review of the new parking layout.

3. The “EXISTING FENCE AND ENTRY GATES” shown on A001 are not shown on the last approved development package, DP22-0243. Either provide an approved DP that shows the fence and entry gates reflected on A001 or submit a new DP for review of the new layout.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
05/28/2024 Water - PDSD REQUIRES RESUBMIT Reduced pressure backflow prevention assemblies are required at the water meter for apartment buildings that have common laundry facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf
04/24/2024 PDSD Application Completeness Express REVIEW COMPLETED