Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0424-00723
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/01/2024 | Water - PDSD | APPROVED | SEE INTERNAL NOTES - MASTER SET OF CONSTRUCTION PLANS ARE LOCATED AT TC-COM-0424-00723 (810 E BENSON HY Unit:BLDG 1) with reviews to be performed for permit TC-COM-0924-01706 (810 E BENSON HY Unit:BLDG 2 TUCSON, AZ 85713) | ||
| 10/04/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | SEE INTERNAL NOTES - MASTER SET OF CONSTRUCTION PLANS ARE LOCATED AT TC-COM-0424-00723 (810 E BENSON HY Unit:BLDG 1) with reviews to be performed for permit TC-COM-0924-01706 (810 E BENSON HY Unit:BLDG 2 TUCSON, AZ 85713) | ||
| 10/04/2024 | Commercial Electrical | REQUIRES RESUBMIT | SEE INTERNAL NOTES - MASTER SET OF CONSTRUCTION PLANS ARE LOCATED AT TC-COM-0424-00723 (810 E BENSON HY Unit:BLDG 1) with reviews to be performed for permit TC-COM-0924-01706 (810 E BENSON HY Unit:BLDG 2 TUCSON, AZ 85713) Please address the electrical plan review comments and provide a written response. 1. The previous electrical plan review comments requested clarity and correlations for all the electrical information submitted in the plan set. The plan review comment response stated,” Elec. Scope of work is to replace the extensive damaged and missing copper circuit wire and electrical fixtures thru-out the entire building”. “Most of the work is new”. For clarity, please provide the additional electrical information on the plans, and or clarify where applicable. See review comments 2 Thru 12. 2. Provide an electrical power and lighting site plan for building 1 and building 2. Show all electrical service equipment locations, including the MDP distribution panels, and indicate New or Existing. 3. It appears per the electrical line diagram that all the electrical distribution for building #2 is new. Please verify that the Grounding Electrode System is intact. Provide a grounding detail on the plans for both buildings as this was probably targeted by the copper thieves mentioned in the response letter. 4. Include load calculations with the distribution panel schedules that correlate with the building load calculations. Include both amps and VA with the panel schedules. Also, for the Unit Panel schedules. 5. Indicate raceway sizes and types for all feeders shown in the electrical line diagrams. 6. The load shown in the panel schedule for ‘House Panel Building #1’ exceeds the rating of the OCPD providing protection for it. Please correct. 7. Please identify all panels with the correct building designation. For example, if the buildings are identified as ‘Building #1’ and ‘Building #2’, correlate the electrical panel identifications with their associated buildings, #1 or #2. Not Building A or B. 8. The Unit load calculations shown on plan sheet ‘E2’ do not correlate with the Unit load calculations shown in the Unit panel schedules on plan sheet’E3’. Please clarify. 9. Provide complete compliance with the 2012 City of Tucson Outdoor Lighting Code for the exterior lighting. 10. Provide a complete luminaire schedule. Also include any new or replaced exterior lighting. 11. Provide complete compliance with the 2018 IECC for the lighting. 12. What building is the enlarged Lobby, Mail Room electrical floorplan associated with? Show this on the plan. Be advised, due to the nature of these review comments and necessary required changes or corrections in order to clarify the scope of work, additional review comments may be generated at the subsequent review. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC, 2012 City of Tucson Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements. |
||
| 10/01/2024 | Commercial Mechanical | REQUIRES RESUBMIT | SEE INTERNAL NOTES - MASTER SET OF CONSTRUCTION PLANS ARE LOCATED AT TC-COM-0424-00723 (810 E BENSON HY Unit:BLDG 1) with reviews to be performed for permit TC-COM-0924-01706 (810 E BENSON HY Unit:BLDG 2 TUCSON, AZ 85713). Replacement of a PTAC unit constitutes new work. Provide specifications for the proposed new units (e.g., Manufacturer, model, SEER2, HSPF2, etc.). Provide ventilation per Section 403.3.1, IMC 2018. |
||
| 10/01/2024 | Commercial Plumbing | REQUIRES RESUBMIT | SEE INTERNAL NOTES - MASTER SET OF CONSTRUCTION PLANS ARE LOCATED AT TC-COM-0424-00723 (810 E BENSON HY Unit:BLDG 1) with reviews to be performed for permit TC-COM-0924-01706 (810 E BENSON HY Unit:BLDG 2 TUCSON, AZ 85713). 1. Clarify the Plumbing Plan Keynotes on sheet A1 and differentiate them from the Floor Plan Keynotes on the same sheet. If any plumbing fixtures, water lines, or waste and vent lines are to be relocated or rerouted, show the new locations and provide details to explain how the new locations will be connected to the existing plumbing system. Reference: Section 107.2.1, IBC 2018. 2. For the use of PEX tubing, provide a branch tube sizing chart showing the correct size of PEX tubing to be used as a substitute for the copper pipe shown on the drawings. Reference: Sections 303.2 and 604.3, IPC 2018. |
||
| 09/30/2024 | Commercial Structural | REQUIRES RESUBMIT | SEE INTERNAL NOTES - MASTER SET OF CONSTRUCTION PLANS ARE LOCATED AT TC-COM-0424-00723 (810 E BENSON HY Unit:BLDG 1) with reviews to be performed for permit TC-COM-0924-01706 (810 E BENSON HY Unit:BLDG 2 TUCSON, AZ 85713) ACTIVITY NO. TC-COM-0424-00723 ADDRESS/PARCEL: (810 E BENSON HY Unit:BLDG 1 TUCSON, AZ 85713) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter. COMMENTS: 1. Per Sheet A2 Plumbing Plan Keynotes, Plumbing Fixtures are being relocated, Sanitary Water Vent pipe being relocated, Hot & Cold water lines are being rerouted, etc. Existing bathrooms being converted into Accessible bathrooms. Please submit Plumbing drawings. 2. Show Floor Clearances and turning radius and shower grab bars and door clear opening in Handicap Bathrooms including the Business Office restroom. 3. In Handicap Units, at Bar Sink Provide drawings that illustrate the ANSI accessible counter on both height and width requirements per 2009 ANSI A117.1 Figure 904.3(B). Provide drawings as well illustrating the leg clearances under the counter. 4. At Business/Office reception desk, for both employees and customers Provide drawings that illustrate the ANSI accessible counter on both height and width requirements per 2009 ANSI A117.1 Figure 904.3(B). Provide drawings as well illustrating the leg clearances under the counter. 5. At Laundry, Lounge and Exercise Rooms; Restroom to be Accessible. Please resolve this issue. 6. Building #1: with 52 units, 4 Accessible Units are required, the rest are to be Type B Units. Building #2: with 46 Units, 2 Accessible Units are required, the rest are to be Type B Units. That is a total of 6. You show 5, please resolve this discrepancy. Ideally, each building should have their own Accessible units within them. However, we will agree with you to locate all 6 Accessible Units in Building #1. On each Unit floor plan, identify/label which are the Accessible Unit and which are the Type B Units. Specify exactly that you will be proposing for the Type B Units. 7. Within the Accessible units, one roll-in shower per Table 1107.6.1.1 shall be required. Please locate/label this on the drawing. 8. Show the accessible route from the handicap parking stalls. Show ramps along the route. Please locate/label the handicap sign on post as well and provide drawings for the sign and graphics (including the stall plan graphic). 9. Please provide the Occupant Load. 10. Please resubmit. |
||
| 09/17/2024 | Fire New Construction | REQUIRES RESUBMIT | --Please correct the fire alarm code reference on sheet AS.1. It currently states 1103.7.5.10. It should be 1103.7.5. Thank you. john.vincent@tucsonaz.gov 5203495581 SEE INTERNAL NOTES - MASTER SET OF CONSTRUCTION PLANS ARE LOCATED AT TC-COM-0424-00723 (810 E BENSON HY Unit:BLDG 1) with reviews to be performed for permit TC-COM-0924-01706 (810 E BENSON HY Unit:BLDG 2 TUCSON, AZ 85713) |
||
| 10/01/2024 | Site Zoning | REQUIRES RESUBMIT | SEE INTERNAL NOTES - MASTER SET OF CONSTRUCTION PLANS ARE LOCATED AT TC-COM-0424-00723 (810 E BENSON HY Unit:BLDG 1) with reviews to be performed for permit TC-COM-0924-01706 (810 E BENSON HY Unit:BLDG 2 TUCSON, AZ 85713) ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: TC-COM-0424-00723 & TC-COM-0924-01706 810 E BENSON HY .- C-2 Site Fence (2nd Review) TRANSMITTAL: October 1, 2024 This site is located in the C-2 zone (UDC 4.7.21). 1. This comment was not addressed correctly. The site plan shown on sheet AS.1 shows angled vehicle parking along the northwest end of BLDG 2 and the last approved DP does not. A revision to the DP is required. The parking layout shown on A001 does not match what is shown on the last approved development package, DP22-0243. Either provide an approved DP that shows the layout reflected on A001 or submit a new DP for review of the new parking layout. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 09/03/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |