Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0424-00722
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/28/2024 | Commercial Mechanical | APPROVED | |||
| 05/28/2024 | Commercial Plumbing | APPROVED | |||
| 05/24/2024 | Commercial Structural | APPROVED | |||
| 05/23/2024 | Site Zoning | APPROVED | |||
| 05/22/2024 | Site Engineering | NOT REQUIRED | |||
| 05/28/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/23/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 The Breaker panel cannot be located in the bathroom. NEC 240.24(D) and (E). 2 Provide for combination arc fault circuit breakers as applicable per NEC 210.12. 3 Provide for a GFI protected outlet for the dishwasher per NEC 210.8(D). 4 Verify that there is a GFI protected receptacle on the roof for Mechanical equipment maintenance per NEC 210.63. 5 Provide for a Dark Sky compliant exterior egress luminaire. 6 Provide for interior luminaire to comply with the 2018 IECC section R404.1. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC, 2012 City of Tucson Outdoor Lighting Code. |
||
| 04/25/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 04/24/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |