Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0424-00722
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/28/2024 Commercial Mechanical APPROVED
05/28/2024 Commercial Plumbing APPROVED
05/24/2024 Commercial Structural APPROVED
05/23/2024 Site Zoning APPROVED
05/22/2024 Site Engineering NOT REQUIRED
05/28/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
05/23/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 The Breaker panel cannot be located in the bathroom. NEC 240.24(D) and (E).

2 Provide for combination arc fault circuit breakers as applicable per NEC 210.12.

3 Provide for a GFI protected outlet for the dishwasher per NEC 210.8(D).

4 Verify that there is a GFI protected receptacle on the roof for Mechanical equipment maintenance per NEC 210.63.

5 Provide for a Dark Sky compliant exterior egress luminaire.

6 Provide for interior luminaire to comply with the 2018 IECC section R404.1.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC, 2012 City of Tucson Outdoor Lighting Code.
04/25/2024 Fire New Construction REVIEW COMPLETED
04/24/2024 PDSD Application Completeness REVIEW COMPLETED