Permit Number: TC-COM-0424-00716
Parcel: 138144530

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0424-00716
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/07/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Provide documentation from the manufacturer of the service equipment in order to verify that the service equipment is manufactured with the provision for the bus extension. Otherwise, provide for a field evaluation after the tap is performed by a NRTL agency in order to re-certify the listing of the service equipment. NEC 110.3 and 230.66.

2 What is protecting the feeders for the new panel ‘EV’ ? NEC 240.4.

Ref; 2018 IBC section 107.2.1, 2017 NEC.