Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0424-00716
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/07/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/07/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Provide documentation from the manufacturer of the service equipment in order to verify that the service equipment is manufactured with the provision for the bus extension. Otherwise, provide for a field evaluation after the tap is performed by a NRTL agency in order to re-certify the listing of the service equipment. NEC 110.3 and 230.66. 2 What is protecting the feeders for the new panel ‘EV’ ? NEC 240.4. Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
| 04/22/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |