Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0424-00711
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/01/2024 | Commercial Electrical | APPROVED | |||
| 09/27/2024 | Commercial Structural | APPROVED | |||
| 10/01/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/30/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Heavy-duty appliances (e.g., a gas-fired range) locate under a non-listed Type I hood require a minimum exhaust flow rate 400 CFM/foot. [Initial comment: Provide the specifications and construction details for the existing hood. Unless the existing kitchen hood is a Type I and has been factory-built and tested in accordance with UL 710, the minimum air flow rates shall conform to the requirements of Section 507.5.3, IMC 2018. Reference: Section 507.1, IMC 2018.] | ||
| 09/30/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. The pipe sizes shown for the natural gas system do not come from Table 402.4(2), 2018 IFGC. Verify that the available gas pressure is adequate for operation of all of the appliances when operating simultaneously. Reference: Section 402.1, IFGC 2018. [Initial comment: Provide a schematic diagram of the natural gas distribution system showing the pipe sizes and pipe material, the appliance loads, and the developed length from the gas meter to each appliance. Reference: Section 402, IFGC 2018.] 2. Specify the gravity grease interceptor (they are not specified by grease capacity and flow rate, see Section 1003.3, IPC 2018, as amended by the City of Tucson). Show the location for the proposed gravity grease interceptor and the piping revisions needed to install the unit. [Initial comment: The minimum size for a hydromechanical grease interceptor is rated at a minimum of 25 GPM with a grease capacity of 50 pounds. A maximum of 4 plumbing fixtures may discharge to a hydromechanical grease interceptor. A dishwasher may not discharge to a hydromechanical grease interceptor; a gravity grease interceptor must be used. Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.] |
||
| 09/30/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 09/03/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |