| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/14/2025 | Water Sterilization Report (Deferred Submittal) Express | APPROVED | |||
| 04/14/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/14/2025 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | The air balance report shows that EF-1 is not able to achieve more than 50% of the design exhaust flow rate. The engineer of record shall review the situation and determine the course of action prior to the air balance report being resubmitted. Reference: Section 403.3.1.5, IMC 2018. | ||
| 04/12/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |