Permit Number: TC-COM-0424-00709
Parcel: 124062210

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0424-00709
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2025 Water Sterilization Report (Deferred Submittal) Express APPROVED
04/14/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/14/2025 Air Balancing/Commissioning Report (Deferred Submittal) Express REQUIRES RESUBMIT The air balance report shows that EF-1 is not able to achieve more than 50% of the design exhaust flow rate. The engineer of record shall review the situation and determine the course of action prior to the air balance report being resubmitted. Reference: Section 403.3.1.5, IMC 2018.
04/12/2025 PDSD Application Completeness Express REVIEW COMPLETED