Permit Number: TC-COM-0424-00648
Parcel: 13323164A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0424-00648
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/18/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 6/14/2024 3:41:47 PM
1. RESOLVED
2. RESOLVED
3. RESOLVED
4. RESOLVED

5. FCCS - PROJECT ADDRESS: The address provided on Cover Sheet FCCS (2020 S. Muskogee Ave, Tahlequah, OK 74464) does not match the project address on the title block (7150 E Speedway Blvd, Tucson, AZ 85710). Construction documents are site-specific and it is not permissible to re-use drawings at multiple locations. Please
revise the address on the cover sheet to match the address of the building application. [EDIT: Conflicting addresses have been listed here for clarification.]

6. FSS0 - CONFLICTING INFORMATION: Under "Canopy Lateral Loads" on structural general notes Sheet FSS0, ultimate wind speed is called out as 115 mph. This conflicts with the general notes provided by the canopy manufacturer on Sheet FCS1.3 that states that canopies are designed for an ultimate wind speed of 103 mph. Please confirm which notes control and revise to resolve this conflict.

7. RESOLVED
8. RESOLVED



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 6/17/2024 9:22:33 AM
1. Unresolved - General: Include the details showing compliance with the envelope and the mechanical provisions of the 2018 IECC sections C402, C403. The plans do not include the insulation R-Values of the walls and ceiling or the UFactors of the windows and doors. If the envelope components do not meet the prescriptive values, please submit the 2018 COMcheck for the envelope.

2. Resolved - Sheet FSCS: If all canopy documents are included in the construction drawings, please remove the Fuel Station Canopy from the list as a deferred submittal. (2018 IBC section 107)

3. Unresolved - Sheet FSCS: Include a scope of work, if fire alarms and sprinklers are being installed, and the allowed vs actual area, height, and number of stories. (2018 IBC sections 107, 501, 504, 506) Information was not included.

4. Unresolved - Sheet FSA5: Show the accessible route, maneuvering clearances, signage, and accessible service counter details. Include the dimensions of the maneuvering clearance area in front of the toilet room doors. (2018 IBC
section 107, 1104, 1109.12, 1111, 2009 ICC A117.1 sections 402, 403, 404, 404.2.3.2, 703, 904) The accessible route, maneuvering clearances, and accessible counter details were not provided.





Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 6/17/2024 9:21:33 PM
Second Plumbing Review:
Resolved-1)..General: Plumbing plans and or any any plan pages not uploaded to document files. Please upload plan sets for review: -IPC 2018 106.3.1
2). Plan page FSA4: Plan page missing secondary thru wall scupper adjacent to the primary scupper. ( note: the required secondary over-flow can't be located beyond roof in the exterior downspout assembly.) Add a secondary thru wall scupper to the plan page in accordance with -IPC 1106.5 & section 1108
07/16/2024 Site Engineering REQUIRES RESUBMIT 1. The building permit cannot be approved until TD-DEV-0524-00143 has been approved.

Mike Ortiz
michael.ortiz@tucsonaz.gov
07/08/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0424-00648 - TD-DEV-0524-00143
7150 E SPEEDWAY BL. – PAD-3
Fuel Station @ Walmart (2nd Review)

TRANSMITTAL DATE: July 8, 2024

DUE DATE: July 15, 2024

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the P-I zone (UDC 4.7.29). Automotive Minor is a allowed use in the zone (UDC Table 4.8-5), subject to Use Specific 4.9.13.E.

1. Zoning has reviewed this building plan for compliance with Development Package (DP) TD-DEV-0524-00143 and although it appears that the plans match until the DP is approved by all review agencies Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
06/13/2024 PDSD Application Completeness REVIEW COMPLETED