Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0424-00643
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2024 | Commercial Electrical | APPROVED | |||
| 05/10/2024 | Site Engineering | APPROVED | |||
| 05/10/2024 | Site Zoning | APPROVED | |||
| 05/09/2024 | Water - PDSD | APPROVED | |||
| 05/09/2024 | Commercial Mechanical | NOT REQUIRED | |||
| 05/13/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/09/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Clarify why hot water is not being supplied to the service sink (SS). Reference: Section 607.1, IPC 2018. 2. Clarify the plumbing system for the greenhouse. Each plumbing system requires at least one vent that extends to the outside. Reference: Section 918.7, IPC 2018. |
||
| 05/13/2024 | Commercial Structural | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0424-00643 ADDRESS/PARCEL: (2411 E BLACKLIDGE DR TUCSON, AZ 85716) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. COMMENTS: 1. Please include a complete set of construction documents for the Bathroom Structure. 2. Please include drawings depicting anchoring the cargo containers per IBC 1604. 3. Please include a complete set of construction documents for the Green House Structure. If structure is constructed of steel, submit drawings and calculations done by a Structural Engineer with his seal/signature/date on the documents. 4. Please resubmit. |
||
| 04/14/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 04/11/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |