Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0424-00639
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2024 | Commercial Mechanical | APPROVED | |||
| 05/13/2024 | Site Zoning | APPROVED | |||
| 05/10/2024 | Site Engineering | NOT REQUIRED | |||
| 05/13/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/09/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Assign branch circuits and panel designation to the electrical devices shown on the electrical floor plan. Correlate with the panel schedule. NEC art 408.4 2 Verify all branch circuits are Combination Arc Fault protected. NEC art 210. 3 Provide Tamper resistant receptacles. NEC art 210 and 406.12 4 Provide a luminaire schedule and compliance with the 2018 IECC for the lighting. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
||
| 05/09/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Provide plumbing plans for the new work (i.e. modifications to the first floor bathroom), including water isometrics and waste and vent isometrics. Reference: Section 107.2.1, IBC 2018. 2. Specify that all proposed plumbing fixtures shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018. 3. Provide shower valves that comply with the requirements of Section 412.3, IPC 2018. 4. If the shower does not have a prefabricated receptor, provide details to show that the construction of the receptor complies with the requirements of Section 421.5, IPC 2018 5. The presence of a reduced pressure backflow prevention assembly will require the installation of a thermal expansion tank for the storage-type water heater. Reference: Section 607.3, IPC 2018. |
||
| 05/13/2024 | Commercial Structural | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0424-00639 ADDRESS/PARCEL: (4827 E STARFLOWER ST TUCSON, AZ 85756) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. COMMENTS: 1. Include a complete Egress Plan. 2. Include a complete Code Analysis. NOTE: R-3 maximum allowable is 5 clients & R-4 maximum allowable is 10 clients [Indicate the Occupancy Classification, indicate the number of clients on your drawings as well as indicate whether it is Child Day Care, Adult Day Care, Assisted Living, Residential Care, Group Home, Behavioral Health, etc (ensure that your selection confirms what you selected from the City Zoning Code & your State Department of Health Services License Application)]. Obtain the Land Use that you are using from within the City of Tucson Zoning Code (Unified Development Code). Do the clients reside at the facility on a 24-hour basis? Please provide a description of the services that you provide (a description of your daily operation written down to include your time of operation, the type of clients/patients, the type of services, the professionals who will be providing the services, etc). Include a statement as part of your code analysis as to how the facility handles any persons receiving custodial care who require limited verbal or physical assistance responding to an emergency situation to complete building evacuation and self preservation. Specify Condition 1 or Condition 2 per IBC 310 (this will determine the type of fire sprinkler system the fire department will require). 3. On the Site Plan show/indicate the Accessible route from drop off location to the accessible entry door complying to IBC 106 & ANSI A117. In an Emergency, show/locate the gathering area/dispersal area where it is safe from danger minimum 50 ft away from structure per IBC 310.5 and 1028.5. 4. Indicate the clear opening of the doors complying to ANSI A117. 5. Indicate the clear width of hallways. 6. Show/locate the side & back grab bars at the Water Closet as well as at the Shower, make sure to indicate the installation of Structural Backer Board for these grab bars per IBC Chapter 11. 7. Provide Emergency Escape & Rescue Openings per R310 at every bedroom/sleeping space. On the drawing adjacent to the opening(s), indicate the clear opening for both horizontally and vertically and provide the dimension from the finish floor to the bottom of the opening. Indicate if there are obstacles on either side of the opening. 8. Fire Sprinkler is required per IBC 420 and processed as a separate permit. Submit the drawings to Tucson Fire Department for review and approval. They will conduct fire inspection, the inspection approval document will be required as a deferred submittal before issuing the Certificate of Occupancy. 9. A fire alarm is required [IBC 907], If they exist...indicate them on your drawing. If not...please indicate how this is addressed. 10. Illumination with emergency backup power is required in all components of the means of egress system [IBC 1008]. Please locate/identify/label those equipments including the Lighted Exit Sign(s), Emergency Light(s) w/ battery backup, Fire/Audible/Smoke Alarms if applicable, Fire Extinguisher on your plan (to be inspected by Tucson Fire Department). 11. Electrical work (conductors/wiring/breaker ONLY) related to the installation will be inspected by City of Tucson inspectors, show on your plans so that our inspectors will know what wiring/breaker to inspect and shall also be reviewed as part of this permit. 12. Any new work must be included as part of this building permit. 13. A Final inspection will be conducted by our inspectors prior to issuance of the Certificate of Occupancy. 14. An Operator's License must be applied for with the State, the absence of this license shall void this building permit. 15. Submit a draft copy of the State Department of Health Services License application confirming the exact use title for the certificate of occupancy document. 16. Please resubmit. Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976 |
||
| 04/25/2024 | Fire New Construction | REQUIRES RESUBMIT | Update Occupancy Type (including conditions if applicable), occupant load (proposed number of residents/staff), etc. Questions: patricia.shelton@tucsonaz.gov |
||
| 05/09/2024 | Water - PDSD | REQUIRES RESUBMIT | Reduced pressure backflow prevention assemblies are required at the water meter for licensed, personal care facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf. | ||
| 04/11/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |