Permit Number: TC-COM-0424-00626
Parcel: 137070530

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0424-00626
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2024 Site Zoning APPROVED
04/24/2024 Site Engineering NOT REQUIRED
05/13/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/13/2024 External Reviewers - Stantec REQUIRES RESUBMIT April 18, 2024
1st Review

Chuck Meyer Architect, LLC
Attn: Chuck Meyer
11598 W. Rock Village St.
Marana, Arizona 85658

Re: ALIGN HEALTH AND SPINE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0424-00626
Stantec Project Number: 185215066
Stantec File Number: TUC-24-035

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 2,142 31 Yes No
Separate Permits: Automatic fire sprinklers.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that a permanently mounted disposable cup dispenser is installed adjacent to the cooler with the dispensing end between 34” and 48” above the floor. [Ref. City of Tucson Policy 2008-21(E)]

STRUCTURAL COMMENTS

There are no comments.
MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P1

1. The plumbing plan is missing the water line for the point use water cooler in the reception area as shown on the architectural sheets.

2. The plumbing keynotes for the plumbing plan are cut-off after keynote 10. Please revise and resubmit.

ELECTRICAL COMMENTS

Sheet E2.0

1. Plans indicate what looks to be the garbage disposal switched outlet in the adjacent tenant suite as being connected to circuit 38 in panel L2. The occupants of this suite do not have ready access to the breaker for this branch circuit due to panel L2 being relocated in the proposed tenant improvement suite. Please recircuit this outlet to a panel in this suite. [Ref. NEC 2017 Art. 240.24 (A)]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922