Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-0424-00621
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/22/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
05/22/2024 | Commercial Building | REQUIRES RESUBMIT | Please submit your revised documents along with a detailed response letter, which states how all Building Review Section comments were addressed. 1. Sheet TY-500: Please amend plans to show the location and type of access controlled doors on the Exiting Plan. IBC 107.2.3 2. Sheet TY-400: Please explain how B doors will always allow free egress by mechanical means from secure side. What releases the electromagnetic locking system? IBC 1010.1.9.10 Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
05/20/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Indicate where the System or the Door Control Cabinet receives line voltage input power from... Be advised any electrical design required for the installation of line voltage (120-480 Volt) outlet(s) will require complete electrical plans sealed by a Registrant registered in the State of Arizona. Ref; 2018 IBC 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Electrical Plan Submittal Requirements. |
||
05/14/2024 | Fire New Construction | REVIEW COMPLETED | |||
05/07/2024 | PDSD Application Completeness | REVIEW COMPLETED |