Permit Number: TC-COM-0424-00621
Parcel: 12701005D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0424-00621
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
05/22/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised documents along with a detailed response letter, which states how all Building Review Section comments were addressed.
1. Sheet TY-500: Please amend plans to show the location and type of access controlled doors on the Exiting Plan. IBC 107.2.3
2. Sheet TY-400: Please explain how B doors will always allow free egress by mechanical means from secure side. What releases the electromagnetic locking system? IBC 1010.1.9.10

Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
05/20/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Indicate where the System or the Door Control Cabinet receives line voltage input power from... Be advised any electrical design required for the installation of line voltage (120-480 Volt) outlet(s) will require complete electrical plans sealed by a Registrant registered in the State of Arizona.

Ref; 2018 IBC 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Electrical Plan Submittal Requirements.
05/14/2024 Fire New Construction REVIEW COMPLETED
05/07/2024 PDSD Application Completeness REVIEW COMPLETED