Permit Number: TC-COM-0424-00620
Parcel: 122173090

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0424-00620
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/25/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/25/2024 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0424-00620
ADDRESS/PARCEL: (3139 E BELLEVUE ST TUCSON, AZ 85716)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:
1. Please submit a site plan. Locate and label/number each canopy. Place dimensions on each canopy as well as dimensions for setbacks or required clearances to adjacent structures.
2. Submit electrical drawings and locate and label the light locations. Submit an image of the light fixtures being used, their lumens as well as the kelvin temperature of the light source.
3. Please resubmit.
04/11/2024 Fire New Construction REQUIRES RESUBMIT -Could not locate where the canopies will be installed. Include the location of the canopies on the site plan. I will need to verify locations based on fire aerial access requirements.
john.vincent@tucsonaz.gov
5203495581
04/24/2024 Site Engineering REQUIRES RESUBMIT 1. Provide a site plan that shows the locations of the shade canopies.
2. Adding shade canopies to the site requires a revision to the approved development package, DP20-0153. The shade canopies must be shown on a site plan and the site plan in the building permit application must match the one provided in the development package.

Lianne Evans
lianne.evans@tucsonaz.gov
04/24/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-COM-0424-00620
3139 E BELLEVUE ST. – R-3
Adding 16 Shade Canopies to the parking lot. (1st Review)

TRANSMITTAL DATE: April 24, 2024

Please resubmit revised drawings detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-3 zone (UDC 4.7.12). Multifamily is a permitted use in this zone (Table 4.8-2). See Use-Specific Standard 4.9.7.B.6.

1. The approved development package for this site does not show any shade structures within the parking area. A revision to DP20-0153 clearly shown the proposed shade structures is required prior to approval of this building permit.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
04/10/2024 PDSD Application Completeness Express REVIEW COMPLETED