Permit Number: TC-COM-0424-00594
Parcel: 134161990

Address:
7401 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0424-00594
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2024 Site Zoning APPROVED
04/22/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
04/22/2024 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0424-00594 (7401 E 22ND ST TUCSON, AZ 85710)
ADDRESS/PARCEL: TC-COM-0424-00594 (7401 E 22ND ST TUCSON, AZ 85710)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:
1. Locate and label the cash register counter on the Floor Plan.
2. Indicate on the Floor Plan where power is routed to the cash register.
3. Provide drawings illustrating how the cash register counter/cabinet is meeting the ICC ANSI A117.1 required height and the clear width.
4. On the Floor Plan, provide information on power plan such as the receptacles, switches, etc.
5. Are the base cabinets internally lit.
6. Are the wall cabinets have lights.
7. Provide a Reflected Ceiling Plan illustrating the existing lights.
8. Are the existing lights (item #7 above) correspond to the display cabinets below or will additional lights be necessary to meet the needs of the display cabinets. If so, please provide the electrical drawings for this.
9. Item J, Bottle Water. Is this a water dispenser. Provide information on how it is to be powered electrically.
10. Mop Sink: is this new, if it is please provide drawing for water and sewer connections.
11. Smoking area requires a certain volume of exhaust. Please provide information illustrating how you are complying with this.
12. Please resubmit.
04/08/2024 Fire New Construction REVIEW COMPLETED
04/05/2024 PDSD Application Completeness REVIEW COMPLETED