Permit Number: TC-COM-0424-00575
Parcel: 13305054M

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0424-00575
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/11/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 6/10/2024 11:48:18 AM
1. Resolved - Sheet CS1: The incorrect accessibility code is stated. The currently adopted accessibility code is the 2009 ICC A117.1.

2. Resolved - Sheet CS1: List the prior use of the building. If the new use is a change of occupancy classification, correct the existing building alteration level to change of use and revise all affected sheets. (2018 IEBC sections 302.6, 601,605)

3. Resolved - Sheet CS1: Include the allowed area, height, and number of stories. (2018 IBC sections 503, 504, 506)

4. Resolved - Sheet CS1: Include the office space and break room in the occupant load calculations. Office spaces are to be calculated at 1 person per 150 sf and the breakroom is to be calculated at 1 person per 15 sf. (2018 IBC section 1004, Table 1004.5)

5. Unresolved - Sheet A1.3: Show the accessible routes, maneuvering clearances, clear floor spaces at the lavatories, and the turning circle outside of the toilet compartment. (2009 ICC A117.1 section 304, 305, 402, 403, 404, 603.2.1, 606) The incorrect maneuvering clearance floor spaces on the push and pull sides of the men’s toilet room door are shown.

6. Unresolved - Sheets A1.1, A3.1: Include the energy code compliance of the envelope and fenestration. (2018 IECC section C402. The energy code compliance details for the new doors in the store front are not included in the COMcheck. The plans and COMcheck need to include the details for any newly insulated or re-insulated envelope assemblies, newly conditioned spaces, and the U-Factors of both the windows and doors.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 6/10/2024 7:52:48 PM
Second Plumbing Review:
Unresolved_1). General: Need to address Building plan review comment # 5: Plumbing review is directly affected by these comments please address in accordance with -2018 IPC section 404 Resolved_2). Plan sheets A1.3 detail 1 & MP2: The minimum clearance distance from lavatory center to adjacent obstruction
needs to be 15" minimum, the wall accessory encroaches this minimum distance. Relocate the wall accessories to meet the minimum clearances stated in -2018 IPC 405.3.1
06/04/2024 PDSD Application Completeness Express REVIEW COMPLETED