Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0424-00575
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/30/2024 | Site Zoning | APPROVED | |||
| 04/25/2024 | Site Engineering | NOT REQUIRED | |||
| 04/30/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/18/2024 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Denied Reason: Date Completed : 4/13/2024 5:46:05 PM 1. GENERAL - UPDATES: For project updates, please submit sheets with all changes clearly marked in revision clouds. Please provide a written response to each comment; updates without a clear response to all comments may not be reviewed. If you have any questions regarding the comments, you may contact me directly. Updates may result in additional comments. 2. GENERAL - FIRM REGISTRATION: Per the Arizona Revised Statutes, Chapter 32, Rule 141, a firm shall not engage in the practice of any board-regulated profession or occupation unless the firm is registered with the board”. The construction documents must indicate the name and registration number of the engineering firm by which the signing engineer is employed. Please update the construction documents to comply with this provision. Refer to the Arizona State Board of Technical Registration (https://btr.az.gov/public/registered-firm-branch-search) for more information. 3. S1.1 - CURRENT CODE: The currently adopted building code for the City of Tucson is the 2018 International Building Code. Please update the Special Inspection Notes on Sheet S1.1 to comply with this code. 4. S1.1 - MISSING DOCUMENT: The structural general notes, Section 6: Design Criteria, Note 6.g reference structural calculations to support the Seismic Response Coefficient ("See Calcs"). If calculations have been prepared as part of the construction documents, please provide them to the City of Tucson for review. Building(B) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 4/9/2024 11:52:16 AM 1. Sheet CS1: The incorrect accessibility code is stated. The currently adopted accessibility code is the 2009 ICC A117.1. 2. Sheet CS1: List the prior use of the building. If the new use is a change of occupancy classification, correct the existing building alteration level to change of use and revise all affected sheets. (2018 IEBC sections 302.6, 601, 605) 3. Sheet CS1: Include the allowed area, height, and number of stories. (2018 IBC sections 503, 504, 506) 4. Sheet CS1: Include the office space and break room in the occupant load calculations. Office spaces are to be calculated at 1 person per 150 sf and the breakroom is to be calculated at 1 person per 15 sf. (2018 IBC section 1004, Table 1004.5) 5. Sheet A1.3: Show the accessible routes, maneuvering clearances, clear floor spaces at the lavatories, and the turning circle outside of the toilet compartment. (2009 ICC A117.1 sections 304, 305, 402, 403, 404, 603.2.1, 606) 6. Sheets A1.1, A3.1: Include the energy code compliance of the envelope and fenestration. (2018 IECC section C402. Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Denied Reason: Date Completed : 4/15/2024 4:53:13 PM 1. General - Provide Tie down detail for RTU - 2018 IMC Section 301.15 Wind resistance and 2018 IMC Section 301.18 Seismic resistance. Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 4/4/2024 2:29:00 PM 1. On sheet E3.1 ELECTRICAL SCHEDULES, Panel D is wrongly named P. Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 4/15/2024 9:42:43 PM First Plumbing Review: 1). General: Need to address Building plan review comments 1 & 5: Plumbing review is directly affected by these comments please address in accordance with -2018 IPC section 404 2). Plan sheets A1.3 detail 1 & MP2: The minimum clearance distance from lavatory center to adjacent obstruction needs to be 15" minimum, the wall accessory encroaches this minimum distance. Relocate the wall accessories to meet the minimum clearances stated in -2018 IPC 405.3.1 |
||
| 04/14/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 04/02/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |