Permit Number: TC-COM-0423-01157
Parcel: 11811015Q

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0423-01157
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2023 Site Zoning APPROVED
05/23/2023 Site Engineering NOT REQUIRED
06/21/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
06/21/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0423-01157

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Denied
Reason:
Date Completed : 6/21/2023 10:37:12 AM
1. Refer to Structural Calculations submitted; the calculations show conveyors supports at certain c/c spacing. No locations on Plan are shown for these supports. Provide Structural Drawing showing locations of the supports.
Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.

Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 6/14/2023 3:24:29 AM
1. Clarify if this conveyor system replaces an existing conveyor. If so, show the layout of the old conveyer or indicate the upgrade did not change the layout. Update the scope of work to indicate new or replacement systems.
2. Provide a floor plan of the warehouse and show any additional existing equipment or racking. It is unknown if the conveyer creates exiting issues for the existing space such as dead end corridors. 2018 IBC 1020.4.
3. Provide an occupancy count on the egress plan for the warehouse. 2018 IBC 1004.5
4. Provide an enlarged floor plan for the area where the new air compressor units are located. Clarify if this compressor replaces an existing unit.
5. A sheet index is provided however the drawings are not labeled as such and it is confusing. Coordinate the drawings and the details so the information is consistent or separate out the manufactures shop drawings from the architectural drawings.
6. Clarify if there is to be any new electrical installed or electrical connections as part of this submittal.

Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 6/6/2023 10:43:10 PM
Approved/subject to field approval

Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 6/9/2023 2:07:12 PM
Electrical Review
By: Ron Ross PE
No electrical drawings or information provided. An Electrical permit is denied.
Equipment installation may not actually require an electrical permit. Consult with local AHJ.
05/24/2023 Fire New Construction REVIEW COMPLETED
05/05/2023 PDSD Application Completeness REVIEW COMPLETED