Permit Number: TC-COM-0423-01156
Parcel: 137040540

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0423-01156
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/11/2023 Commercial Plumbing REQUIRES RESUBMIT 1. Comment not addressed. [Initial comment: Relocate the backflow assembly to be directly after the new water meter. Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf]
2. Comment not addressed. [Initial comment: Specify the material used for the water service pipe. Reference: Section 107.2.1, IBC 2018.]
3. Comment not addressed. [Initial comment: Provide the size of the replacement water service pipe. A 5/8” water meter is allowed to supply up to 20 GPM; verify that the increased pipe length will not result in inadequate water pressure. Reference: Section 604.7, IPC 2018.]
07/06/2023 PDSD Application Completeness Express REVIEW COMPLETED