| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/16/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/16/2023 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Specify the material used for the water service pipe. Reference: Section 107.2.1, IBC 2018. 2. Provide the size of the replacement water service pipe. A 5/8” water meter is allowed to supply up to 20 GPM; verify that the increased pipe length will not result in inadequate water pressure. Reference: Section 604.7, IPC 2018. |
||