Permit Number: TC-COM-0423-01154
Parcel: 11619175C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0423-01154
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/02/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Janet Matz
jmatz@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 5/24/2023 1:56:39 AM
no structural work was indicated as part of this submittal



Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 8/1/2023 11:03:33 AM
1. Original comment: Provide a second floor plan for the top of the existing curved stairway that is being partially closed. Indicate the use for this space on the plans. Response: Please see the new Sheet A2.2 Enlarged Floor Plan showing the Second level for the staircase. The space will be used for storage.

The existing stair to the north appears to be completely enclosed. No door or access was found for this area on the first floor plan and the newly provided second floor plan indicates the area being walled off and not part of the storage. If the area is to be enclosed, it would be considered concealed space and would be required to follow the requirements of 2018 IBC section 718. Clarify if this is to be a concealed space and if so indicate the required fire blocking per 718.2. Provide dimensions for the new walls to be built on the second floor landing area as shown on the second floor plan. Indicate if the two adjacent rooms shown will be used for storage and label accordingly.

Only one of the rooms have been labeled on the floor plan sheet A2.2, the use of the second area is not defined. Define the use of BOTH areas.

1. Original comment: Provide a life safety and exiting plan on the drawings that indicate the travel distances, location of the exits and the occupancy of each storage area. Show the location of the existing exit lights and emergency lighting/wall packs on the plans. Identify the four exits that are indicated on sheet A1.0 and update the required number of exits. This plan should include the existing second floor rooms that are at the top of the curved stairway, as well as any adjacent areas not shown on the partial floor plan that are required to exit through the renovated area. It appears that the new storage room 121 was an exit path and the stair 122 leads directly into the space. 2018 IBC 1017.2. Response: Please see the new A1.1 Life Safety Plan indicating travel distances to each of the exits from the business and fitness center. Additionally, new and existing exit light locations have been noted along with the four indicated exits. An exit path has been shown from Room 201 second floor stair and out to the nearest exit. Emergency lighting has been indicated. The Occupancy of each storage area has been indicated on the A1.1 Life Safety Plan, and the overall occupancy has been adjusted accordingly on Cover Sheet A1.0.

The new life safety plan will need to indicate the second floor and the travel distance from the most remote point on the second floor to the exit discharge to the exterior. 2018 IBC 1017.2. Additionally the plan indicates the storage room 201 is only 154 sf however the second floor is shown much large then that. Provide a revised square foot and occupancy count for this area.

Only the sf and occupancy was updated for the second floor storage area. Provide a life safety plan for the second floor and the travel distances from the most remote point to verify code compliance.




Mechanical(M) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 5/24/2023 1:55:39 AM



Electrical(E) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved with Comments
Reason:
Date Completed : 7/22/2023 3:41:14 AM
The means of egress lighting under normal power and emergency power will be verified at inspection for the existing spaces. All spaces that are part of the means of egress shall be provided with lighting in accordance with the 2018 IBC section 1008. 2018 IEBC section 805.7.1.



Plumbing(P) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 7/22/2023 3:41:29 AM
07/28/2023 PDSD Application Completeness REVIEW COMPLETED