05/24/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0423-01142

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Janet Matz
jmatz@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 5/24/2023 4:00:27 AM
no structural work was included in this submittal


Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 5/24/2023 3:59:19 AM
1. Update the summary of governing regulations on sheet A1.0 to indicate the ICCI A117.1- 2009 for accessibility and update the electrical to indicate the National Electrical Code.
2. Provide a life safety and exiting plan on the drawings that indicates the travel distances, location of the exits and the occupancy of each separate area. Show the location of the existing exit lights and emergency lighting/ wall packs on the plans. 2018 IBC 1017.2.
3. Note on the finish schedule sheet A4.0 that all interior finishes will be in accordance with 2018 IBC 803.1.
4. Clarify if there are any special requirements for protection such as lined walls for the X-ray machine installed in the procedure room 109. If so, include these in the plans.
5. Indicate on the drawings that fire extinguishers shall be installed in accordance with 2018 IFC section 906.2.
6. Note on the drawings that any openings, existing or new within the fire rated barrier will be filled to match or exceed the fire rating of the wall. 2018 IBC 714.


Mechanical(M) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 5/24/2023 3:59:54 AM


Electrical(E) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 5/24/2023 3:59:43 AM
1. Indicate the location of an existing emergency light on the exterior at the exit doors to illuminate the landings or indicate new fixtures will be provided. 2018 IBC 1008.3.2 (5).
2. Indicate the location of the emergency lighting in the event of a power failure with battery backup. 2018 IBC 1008.3.1.
3. Indicate the location of all “night lighting” on the plans for egress illumination or indicate light sensors will be used. All rooms and usable floor surfaces in a building shall be equipped with artificial lighting and shall be illuminated at all times that the space is occupied. 2018 IBC 1008.2.


Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 5/21/2023 8:42:10 AM
First Plumbing Review:
1). Vacuum Exhaust detail #202 on plan page P202 can't be plastic - NFPA99 5.1.3.7.7.65
2). Minimum overhead water supply size to the water dispenser needs to be at least 3/8" - IPC 604.5 update plan page P1.0
3). Occupancy load total of 14 is pending building plan review approval, may require service sink & additional restroom fixtures if determined load count is higher. -IPC 403.1