Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0423-01140
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/20/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/20/2024 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Structural(S) Reviewer Janet Matz jmatz@safebuilt.com Denied Reason: Date Completed : 8/20/2024 4:13:05 PM 1. C-100 (Cover Sheet)- Note on the cover sheet that all work will be done in accordance with the following codes as adopted by the City of Tucson: (2018 IBC section 107.2.1) i. 2018 International Building Code 2. C-100 (Cover Sheet)- Indicate on the cover sheet the design criteria for the awning including the live and dead loads, wind speeds and seismic category. (2018 IBC section 107.2.1) 3. C-100 (Cover Sheet)- Update the Table of Contents to match the drawing set. Sheet I-202 is listed in the index but not included in the set, and sheet I-3.02 is included in the set but not listed. (2018 IBC section 107.2.1) Building(B) Reviewer Janet Matz jmatz@safebuilt.com Approved Reason: Date Completed : 8/20/2024 4:12:10 PM |
||
| 08/15/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |