Permit Number: TC-COM-0423-01140
Parcel: 12513015B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0423-01140
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/20/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer (from previous submittal TUC9244001.050223)
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 5/15/2023 12:00:07 AM



Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 7/19/2023 12:18:57 AM




Mechanical(M) Reviewer (from previous submittal TUC9244001.050223)
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 5/14/2023 11:59:48 PM



Electrical(E) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 7/19/2023 12:19:08 AM




Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 7/14/2023 8:26:21 PM
Third Plumbing Review:
1). SAME- Plan page P.1 needs to include the the GPM load that each set roof drains are responsible for. -IPC 1106.2** The GPM loads added to plan page P1 are not correct , 3" rainfall Rate & 1184 sq ft = 37GPM, 3" Rainfall rate & 874 sq ft. = 27
GPM **
2). OK
07/10/2023 PDSD Application Completeness Express REVIEW COMPLETED