Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0423-01140
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/20/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/20/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Structural(S) Reviewer (from previous submittal TUC9244001.050223) Janet Matz jmatz@safebuilt.com Approved Reason: Date Completed : 5/15/2023 12:00:07 AM Building(B) Reviewer Janet Matz jmatz@safebuilt.com Approved Reason: Date Completed : 7/19/2023 12:18:57 AM Mechanical(M) Reviewer (from previous submittal TUC9244001.050223) Janet Matz jmatz@safebuilt.com Approved Reason: Date Completed : 5/14/2023 11:59:48 PM Electrical(E) Reviewer Janet Matz jmatz@safebuilt.com Approved Reason: Date Completed : 7/19/2023 12:19:08 AM Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 7/14/2023 8:26:21 PM Third Plumbing Review: 1). SAME- Plan page P.1 needs to include the the GPM load that each set roof drains are responsible for. -IPC 1106.2** The GPM loads added to plan page P1 are not correct , 3" rainfall Rate & 1184 sq ft = 37GPM, 3" Rainfall rate & 874 sq ft. = 27 GPM ** 2). OK |
||
| 07/10/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |