Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0423-01138
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/14/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
06/14/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Activity Number: TC-COM-0423-01138 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. Structural(S) Reviewer Janet Matz jmatz@safebuilt.com Conditionally Approved Reason: Date Completed : 5/18/2023 4:34:51 AM no structural work has been included with this submittal Building(B) Reviewer Janet Matz jmatz@safebuilt.com Denied Reason: Date Completed : 6/14/2023 12:00:39 AM 1. Show the required clear floor space on the enlarged bathroom plan. Include the sink, water closet, and show the location of the accessories (towel dispenser, soap dispenser, towel hooks) on the plan. The sink clear space is indicated in the details on sheet A6 however the detail does not indicate the clear floor space for the water closet, only a 48” in front of the fixture. 2. The sink at the wine display does not appear to allow a wheelchair to enter and properly turn to access the sink. The 90-degree right turn would require additional floor space in accordance with 304.3. It is unknown if the countertop is to include knee and toe space for turning, or if the bar table bust be smaller in length to allow for additional space on the left side to access the sinks parallel approach. Provide an elevation of the area and include the heights of the sink cabinet and wine display on the drawings. Mechanical(M) Reviewer Janet Matz jmatz@safebuilt.com Denied Reason: Date Completed : 6/14/2023 12:01:17 AM 1. Provide details showing how the ductwork will be provided for the exhaust inlets for the manicure and pedicure stations on the drawings. Exhaust inlets shall be within 12” horizontally and vertically from the point of chemical application. The detail on sheet A4 and the keynote 1 on sheet M1 does not clearly indicate how the required venting locations will be met for all nail stations. The exhaust inlets for the pedicure stations appear to be in the wall about 5 feet from the point of application. 2018 IMC 502.20. Electrical(E) Reviewer Janet Matz jmatz@safebuilt.com Approved Reason: Date Completed : 6/14/2023 12:00:51 AM Plumbing(P) Reviewer Janet Matz jmatz@safebuilt.com Approved Reason: Date Completed : 6/14/2023 12:01:28 AM |
||
06/07/2023 | PDSD Application Completeness | REVIEW COMPLETED |