Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0423-01130
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/13/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/13/2023 | Commercial Plumbing | REQUIRES RESUBMIT | The changes you have made to the plumbing fixture calculation on sheet A1 are incomplete and misleading. Revise the calculations based on A2 Assembly occupancy (1 WC per 40 occupants), not “Retail Area 1 per 100 O.L.” Add a note stating that, “Three single-user restrooms to serve all genders are required and three are provided. The calculation is based on the total occupant load per exception 2, Section 403.1.1, IPC 2021, as approved by the Building Official.” | ||
| 07/12/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |