Permit Number: TC-COM-0423-01130
Parcel: 124150090

Address:
831 E 17TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0423-01130
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/13/2023 Commercial Plumbing REQUIRES RESUBMIT The changes you have made to the plumbing fixture calculation on sheet A1 are incomplete and misleading. Revise the calculations based on A2 Assembly occupancy (1 WC per 40 occupants), not “Retail Area 1 per 100 O.L.” Add a note stating that, “Three single-user restrooms to serve all genders are required and three are provided. The calculation is based on the total occupant load per exception 2, Section 403.1.1, IPC 2021, as approved by the Building Official.”
07/12/2023 PDSD Application Completeness Express REVIEW COMPLETED