Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.6
Permit Number - TC-COM-0423-01128
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.6
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/05/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/05/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. Ref; Electrical Line Diagram. 1. Show the new electrical service riser conduit size and conductor quantity, sizes and types. 2. Show the AIC ratings for the service and sub-panels. 3. Show the existing underground conduit sizes and types for the panel feeders. Ref; Power and Lighting, Site Plan. 1. Are the receptacles, fans and luminaires new to be installed per this project or are they existing? 2. If the work bench area is not enclosed provide WP/ GFI protected outlets and devices, per NEC 210.8(B). 3. If the work areas or building(s) are not totally enclosed where lighting is installed, provide full compliance with the 2012 City of Tucson Outdoor Lighting Code. Include any other exterior lighting on the parcel. 4. What about the Existing Utility Building? Show all electrical devices and lighting connecting to the new sub-panel āCā. 5. Provide compliance with the 2018 IECC if applicable. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC, 2012 City of Tucson Outdoor Lighting Code. |
||
| 10/02/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |