05/17/2023 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections R302.2 and R403.7, IECC 2018 as amended by the City of Tucson. 2. Show the complete specifications for each air conditioner system, including the SEER for each system, and the heating capacity (i.e. fill out the AC installation Template). Reference: Section R103.2, IECC 2018. |
||