Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0423-01088
Parcel: 140190080

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0423-01088
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
05/17/2023 Commercial Mechanical REQUIRES RESUBMIT 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections R302.2 and R403.7, IECC 2018 as amended by the City of Tucson.
2. Show the complete specifications for each air conditioner system, including the SEER for each system, and the heating capacity (i.e. fill out the AC installation Template). Reference: Section R103.2, IECC 2018.
04/28/2023 PDSD Application Completeness REVIEW COMPLETED