| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/18/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/18/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Provide a complete power pole and power line detail. Include the power line height above grade, attachment hardware or method of attachment to the poles, and pole depth. 2 Provide a manufactures cut sheet for the overhead feeder cable showing all the information required per NEC 310.120. 3 Verify compliance with NEC art 225.18. 4 The TEP SR cut sheet is incomplete. Where are the note descriptions. Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
| 04/19/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |