Permit Number: TC-COM-0423-01051
Parcel: 13313005J

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0423-01051
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
07/20/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 7/20/2023 9:12:59 AM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall
not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 7/13/2023 12:28:30 PM
1. Sheet A-A9.1: The level 2 staff restroom is not sized appropriately. The water closet vanity is within the clear floor space of the toilet. Provide a correctly sized restroom in accordance with 2010 ADAAG Section 604.3.2. NOT COMPLIED
Note: The 60"x60" clear floor space does not measure to that size and is incorrectly sized. Provide a clear floor area and a properly sized accessible restroom in accordance with 2010 ADAAG Section 604.3.2
1. Sheet A-B9.0: The level 2 restroom is not sized appropriately. The water closet vanity is within the clear floor space of the toilet. Provide a correctly sized restroom in accordance with 2010 ADAAG Section 604.3.2. NOT COMPLIED
Note: The 60"x60" clear floor space does not measure to that size and is incorrectly sized. Provide a clear floor area and a properly sized accessible restroom in accordance with 2010 ADAAG Section 604.3.2


Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 7/13/2023 7:25:29 PM
All corrections complied
Approved/subject to field approval



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 7/15/2023 6:19:00 PM



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 7/14/2023 11:28:02 PM
Second Plumbing Review:
1). OK
2). OK
3). SAME-plan pages A-A4.0 AB4.0, P-A1.9, P-B1.3 needs to detail the primary/secondary scupper & downspout sizes with calculations - IPC 1106.1, 1106.3, 1106.5, 1108 ** Downspout sizes still not shown**
4). Same-add Fixture Spacing Measurements to plan pages A-A9.0 & 9.1 , A-B9.0, & 9.1 -IPC 404.2, 405.3.1 ** Still missing measurements for dual lavatories**
5). OK
6). Same-Food prep/coffee sink on plan pages CS2.0, A-B2.0, P-B1.0, P-B1.1 needs to discharge to a grease interceptor. - IPC 1003.1, Tucson Plumbing Amendments ** Provide Documentation from Utility authority allowing no interceptor as stated
in response**
7).OK
8). OK
9). Same-Plan set needs to be accompanied with a civil site utility piping plan for continuation of sanitary, water & storm -IPC 106.3.1
10). Added Lavatory detail 218 on P2.1 also needs an ASSE 1070 mixing valve -IPC 419.5
07/20/2023 Site Engineering REQUIRES RESUBMIT There are two issued development packages for the site (DP21-0352 and TD-DEV-0423-00224) but neither of them show the new buildings proposed in this plan. Please revise one of the open development packages to include this addition or submit for a new development package for the addition.

Lianne Evans
lianne.evans@tucsonaz.gov
07/18/2023 Site Zoning REQUIRES RESUBMIT This comment was not addressed. Issued DP21-0352 and TD-DEV-0423-00224 in review do not show the configuration on sheet CS.3. until a DP is approved showing the correct configuration Zoning cannot approve this plan.
07/12/2023 PDSD Application Completeness REVIEW COMPLETED