Permit Number: TC-COM-0423-01051
Parcel: 13313005J

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0423-01051
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/02/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer (from previous submittal TUC9241001.071223)
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 7/20/2023 9:12:59 AM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall
not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 8/2/2023 11:23:43 AM



Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 7/13/2023 7:25:29 PM
All corrections complied
Approved/subject to field approval


Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 7/15/2023 6:19:00 PM



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 7/29/2023 4:43:07 PM
Third Plumbing Review:
Copy to clip bo
1). OK
2). OK
3). Now that downspout sizes have been added to plan page A-A4.0 , a 4" down spout is undersized for the downspout that is conveying 290 Gpm. -IPC 1106.3
4). OK
5). OK
6). Same-Food prep/coffee sink on plan pages CS2.0, A-B2.0, P-B1.0, P-B1.1 needs to discharge to a grease interceptor. - IPC 1003.1, Tucson Plumbing Amendments ** Provide Documentation from Utility authority allowing no interceptor as stated in response** ** EMAIL DOCUMENTATION NOT INCLUDED WITH RESPONSE DOCUMENTS**
7).OK
8). OK
9). OK
10). OK -Added Lavatory detail 218 on P2.1 also needs an ASSE 1070 mixing valve -IPC 419.5 **Subject to field inspections**
07/31/2023 Site Engineering REQUIRES RESUBMIT See Zoning Comment
07/31/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0423-01051
7525 E. Speedway Bl. – O-3
New Building - Education (3rd Review)

TRANSMITTAL: July 31, 2023

This comment was not addressed. Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in O-3 zone (UDC 4.7.15), Educational Use: Elementary and Secondary is an allowed use in the zone (UDC Table 4.8-3), subject to Use Specific Standards 4.9.3.D and 4.9.13.K.

1. This comment was not addressed. Issued DP21-0352 and TD-DEV-0423-00224 in review do not show the configuration on sheet CS.3. until a DP is approved showing the correct configuration Zoning cannot approve this plan. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
07/28/2023 PDSD Application Completeness REVIEW COMPLETED