Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0423-01049
Parcel: 11619376C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0423-01049
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2023 Site Engineering APPROVED
05/09/2023 Site Zoning APPROVED
05/17/2023 Commercial Building NOT REQUIRED NOTE: no permit for the original installation, Electrical review is required, NO building review on this permit.
05/18/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
05/18/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

The original plans were sealed by Dennis Coon EE in 2012

1The design changes to the original installation are significant and will require the original approved plans to be shown with the replaced new or modified equipment both structural and electrical, to be clouded and identified with Deltas, including calculations, equipment specifications, all checked, approved and sealed by an Electrical Engineer registered in the State of Arizona. Also, reference ‘Engineering Scope of Work’ Note #3 at the bottom right corner of plan sheet CS-01.

Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
04/20/2023 Fire New Construction REQUIRES RESUBMIT Larger building:
-Provide 6' perimeter pathways IFC 1204.3.1
-Provide 4' interior pathways IFC 1204.3.2
-Provide smoke ventilation requirements 1204.3.3
04/20/2023 PDSD Application Completeness REVIEW COMPLETED