Permit Number: TC-COM-0423-01023
Parcel: 11804181L

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0423-01023
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2023 Commercial Electrical APPROVED
05/15/2023 Commercial Mechanical APPROVED
05/10/2023 Site Engineering NOT REQUIRED
05/17/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/17/2023 Commercial Building REQUIRES RESUBMIT Please provide the following:
1. On the site plan, show the parking for this establishment to include the handicap stalls/striped accessible route & SIGN, bicycle rack, delivery/loading/unloading stall and please do make sure to show your parking calculation. Show the landscaping that you indicated to remain.
2. On the Architectural Floor Plan and the Equipment /Power Plan, locate/identify the grease trap location to match the Plumbing Waste Floor Plan.
3. In your code analysis, you indicate that sprinkler system is not required. The majority of this space is a commercial cooking operation/kitchen. I understand that an Ansul will be installed with the hood of roughly 50 sf in area, what are you to do with the rest of the kitchen 600 sf in area. Please submit evidence why sprinkler would not be required.
4. SIGN ON SEPARATE PERMIT. ENSURE TO INSTALL TIMER AND PROVIDE ELECTRIC POWER SLOT IN YOUR PANEL SCHEDULE.
5. Electrical work related to installation of Emergency Lights, Lighted Signs, Audible Fire Alarm shall also be included in this package as part of the electrical review.
6. Please resubmit.
05/15/2023 Commercial Plumbing REQUIRES RESUBMIT 1. Tucson Water limits 5/8” water meters to maximum demand of 20-GPM. Show that the installation of the new plumbing fixtures when combined with the existing plumbing fixtures will not cause the demand to exceed the allowable limit. Reference: Section 107.2.1, IBC 2018.
2. Correct the tag for the stock pot (P3/Gas Diagram). Reference: Section 107.2.1, IBC 2018.
3. Revise the size of the natural gas pipe serving water heater WH-1 per Table 402.4 (2). Reference: Section 402.4, IFGC 2018.
4. Per Table 402.4 (2), IFGC 2018, a 2” pipe can deliver only 704 CFH with a 0.5”WG drop at a developed length of 250 feet. You show one 2” branch delivering 747 CFH and a subsequent section of pipe delivering 777 CFH.
05/03/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: 1898 S MISSION RD
TC-COM-0423-01023 Zoning C-2

TRANSMITTAL DATE:‎May 3, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Clarify the proposed Use.
1.COMMENT: As it appears that you are proposing a change of use to Food and Beverage Sales : Excluding Large Retail Establishment you will need to do one of the following: 1) Provide a approved C of O for a use that parks at a ratio of 1 space per 300 sq. ft. of gross floor area or more intense, 2) Demonstrate that the required vehicle parking for the use is provided on site, 3) demonstrate that you meet the requirements of UDC Article 3.3.3.H and provide a copy of a lease with the verbiage required in UDC Article 3.3.3.H.9.b or provide a copy of the notarized affidavit as required under UDC Article 3.3.3.H.9.a. This affidavit can be found at: https://www.tucsonaz.gov/files/pdsd/forms/C_of_O_Releif_Affidavit.pdf. Or 4)A new development package will be required.

2.COMMENT: Provide an approved lot split applicant from the city of Tucson.

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
04/17/2023 Fire New Construction REVIEW COMPLETED
04/14/2023 PDSD Application Completeness Express REVIEW COMPLETED