Permit Number: TC-COM-0423-01007
Parcel: 11008304E

Address:
4515 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0423-01007
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/07/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.
1 Please respond to all the previous electrical review comments.
2 In particular, completely verify that the rapid shutdown contactors are installed within or at 1 ft of each PV Array per the requirements of NEC art 690.12, and show the location in relation to each PV Array on the plans.
Ref; 2018 IBC section 107.2.1, 2017 NEC
04/09/2024 PDSD Application Completeness Express REVIEW COMPLETED