Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0423-01007
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/07/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
05/07/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Please respond to all the previous electrical review comments. 2 In particular, completely verify that the rapid shutdown contactors are installed within or at 1 ft of each PV Array per the requirements of NEC art 690.12, and show the location in relation to each PV Array on the plans. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||
04/09/2024 | PDSD Application Completeness | REVIEW COMPLETED |